2 storage of the battery – GE Industrial Solutions LP 33 Series 50 & 60 kVA Installation Guide User Manual
Page 15
Modifications reserved
Page 15/42
OPM_LPS_3UI_50K_60K_0US_V010.doc
Installation Guide LP 33 Series 50-60 kVA
3.3.2
Storage of the battery
In case of extended storage, when the delivery includes maintenance free batteries, keep in mind that
they are subject to auto-discharging process
To avoid permanent damages to the battery, you must observe the following instructions:
x
The storage time without charging the battery depends on the temperature of the storage ambient.
x
The optimal ambient temperature for the batteries is 68°F (20°C).
For storage temperature higher than 68°F (20°C), the storage time will decrease.
x
Each additional 18°F (10°C) over the nominal temperature of 68°F (20°C) will decrease the storage
time, without freshening charge, by half.
In case of a maintenance free battery, the storage time without charging the battery is
approximately:
6 months with storage temperature 68°F (20°C)
3 months with storage temperature 86°F (30°C)
2 months with storage temperature 95°F (35°C)
NOTE !
In case of battery storage pay
attention to:
FRAGILE
SENSITIVE
TO DAMPNESS
TO HEAT
SENSITIVE
TO FROST
SENSITIVE