GE Industrial Solutions LP 33 Series 50 & 60 kVA Installation Guide User Manual
Page 25
Modifications reserved
Page 25/42
OPM_LPS_3UI_50K_60K_0US_V010.doc
Installation Guide LP 33 Series 50-60 kVA
3.7.4
General dates table for current protection and wire sizing
Fig. 3.7.4-1 Common Input Rectifier & Bypass
Fig. 3.7.4-2 Dual Input Rectifier & Bypass (option)
The AC values below are current ratings per phase.
These maximum and nominal ratings should be considered when choosing the
appropriate AC over current protection device.
NEC (National Electric Code) Section 210-20 a rules must be applied.
DC current rating is the maximum battery discharge current which the UPS allows.
AC Input
AC Input Rectifier
AC Input Bypass
DC Input
F2
UPS Model
F1
Nom. Max.
F3 F4
LP 33 Series / 50 kVA
145A
145 A
174 A
139 A
175 A
LP 33 Series / 60 kVA
178 A
178 A
214 A
167 A
210 A
Size of Branch Circuit Over current Protection - All Models:
"CAUTION - To reduce the risk of fire, only connect UPS to a circuit provided with (see below)
maximum amperes branch circuit over current protection in accordance
with the NEC (National Electric Code), NSI / NFPA 70
AC Input
AC Input Rectifier
AC Input Bypass
DC Input
UPS Model
F1 F2 F3
F4
LP 33 Series / 50 kVA
200 A
200 A
200 A
213 A
LP 33 Series / 60 kVA
225 A
225 A
225 A
250 A
Wire sizing according to NEC Section 210-20 (a) Table 310-16
For recommended wiring, see below table.
AC INPUT:
3-Phase, 4 wires plus GND
AC OUTPUT:
3-Phase, 4 wires plus GND
DC INPUT:
3 wires (positive, negative and neutral) plus GND
Use following single copper wire, AWG size (temperature rating of conductor)
UPS Model
Rectifier Input
Bypass Input
AC Output
DC Input
LP 33 Series / 50 kVA
4 x 3/0 (75°C)
4 x 3/0 (75°C)
4 x 3/0 (75°C)
3 x 3/0 (90°C)
LP 33 Series / 60 kVA
4 x 3/0 (90°C)
4 x 3/0 (90°C)
4 x 3/0 (90°C)
3 x 4/0 (90°C)