COMPACT POWER LINE SHELVES – MODEL J85480S1
Rectifier
or
PEM
Feeder-A Feeder-B
AC or DC Input
Feeds
Bus A
Output
Bus B
Output
Two DC Output
Busses
DC Output Connections
Each Output Bus is rated for
100A and up to 2 gage two-
hole lugs.
M6 nuts with conical washers
provided.
Touch-Safe plastic covers
around output buses.
Torque to 50 in-lb
(5.7 nm)
Torque to 50 in-lb
(5.7 nm)
DC Split Output Bus Option
Split Vout ( - ) buses on either
side of the shelf. Vout ( + ) is
common to both sections.
+5V bias maintains I
2
C
communications even during
a feeder fault.
Multiple shelves may not be
paralleled together.
Controllerless Operation
Lists 4 and 6 ship with a jumper
installed on connector J1 pins 21 and
23. This allows the shelf to be powered
without a controller. Remove this
jumper if controller cable installed.
CP843A controller ships with a
connector that plugs into J1 on a List 1
shelf activating the controller.
Lists 7, 9 and 14 require cc848836107
connector be installed in J1 to allow the
shelf to power up without a controller.
L7, L9, L14 P1 Mating connector (pin out is standard 40 position like L4)
Type
Housing
Mating pin
Crimping tool
Individual wire set
AMP 102387-9 RoHS
20-24 awg: 6-87523-9
91517-1
22-26 awg: 6-87756-8
91517-1
40 position Ribbon cable
AMP 1658621-9 e/w 499252-1 (strain relief) RoHS
This connector set is different because it can accept either a ribbon cable or an individual wire mate.