Uninterruptible power supplies, Models and ratings, Run time charts – Powersolve XT Series User Manual
Page 2: Accessory products, Option order codes
Powersolve Electronics Ltd. 8A Arnhem Road, Newbury, RG14 5RU. England
Tel: 01635 521858 Fax: 01635 523771 Email: [email protected]
www.powersolve.co.uk
Uninterruptible Power Supplies
Models and Ratings
MODEL
OUTPUT POWER
OUTPUT CURRENT
AUTONOMY
VA
Watts
(at 230VAC)
(full load)
XT1600
1600VA
1120W
6.9A
7 Minutes
XT3200
3200VA
2240W
13.9A
7 Minutes
XT6000
6000VA
4200W
26.0A
7 Minutes
Run Time Charts
UPS
Model
Standard Run Time in Minutes (Autonomy vs Load)
200VA
400VA
600VA
800VA
1000VA 1600VA 2000VA 2500VA 3200VA 4000VA 5000VA 6000VA
(140W)
(280W)
(420W)
(560W)
(700W) (1120W) (1400W) (1750W) (2240W) (2800W) (3500W) (4200W)
XT1600
86
39
24
17
12
7
+BM1
328
142
90
62
49
30
+BM2
569
264
163
114
86
55
XT3200
201
86
55
39
30
10
12
9
7
+BM3
439
201
122
86
69
43
29
23
18
+BM4
684
325
199
140
108
68
49
38
30
XT6000
453
201
119
84
67
43
30
23
18
12
9
7
+1BM
990
453
288
201
151
97
67
53
43
30
23
18
+2BM
718
453
328
253
151
110
82
67
49
37
30
+3BM
990
600
453
351
214
151
117
92
67
53
47
Accessory Products
XT232
RS232 Option Card (XT6000 Models only)
XT S
SNMP Network Adaptor Option Card replaces USB port, allowing the UPS to be addressed directly on the LAN
XT V
AS400 Volt Free Contact Option Card replaces USB comms port with a 15 way D-type connector
Providing Utility Fail, Battery Low, Bypass & UPS Alarm Contacts
Option Order Codes
Power (VA)
Options
(1)
E.G. XT1600V
XT Series, 1600VA
With AS400 Volt Free Contact Card fitted
Options (Examples)
Add suffix ‘S’ to Model Number - Adds internal SNMP to UPS (in place of USB port)
Add suffix ‘V’ to Model Number - Adds AS400 VFC to UPS for Utility Fail, Bypass, Battery Low and UPS Fault (in place of USB port)
Add suffix ‘X’ to Model Number - Replaces 5 year design life batteries with 10 year
(1) Options should be listed in alphabetical order