beautypg.com

Powersolve XT Series User Manual

Uninterruptible power supplies, Xt series 1.6-6kva true on-line ups, Features

background image

Powersolve Electronics Ltd. 8A Arnhem Road, Newbury, RG14 5RU. England

Tel: 01635 521858 Fax: 01635 523771 Email: [email protected]

www.powersolve.co.uk

Uninterruptible Power Supplies

INPUT
Input Voltage (full load

230VAC version: 160-276VAC

without using batteries)
Input Frequency

45-65Hz

Input Power Factor

>0.98 at full load

Input Protection

Breaker (see notes on next page)

OUTPUT
Output Voltage

230VAC nominal

Output Regulation

±2% of nominal

Output Waveform

Sine Wave

Output THD

<3% linear load

Crest Factor

3:1

Output Protection

Electronic Overload Protection (ultimately by fuse/breaker)

Efficiency (AC-AC)

86% up to 1.5kVA, 90% up to 6kVA

Overload Capacity

See Overload Characteristics

Output Frequency

50/60Hz dependant on input

BATTERY
Internal Battery Type

VRLA 5 year design life. For 10 year option add suffix ‘X’ to model number

Recharge

<8 hours to 90%, standard battery only

Battery String Voltage

48VDC: 1.6kVA, 96VDC: 3.2kVA, 192VDC: 6.0kVA

Autonomy

See Tables

Temperature

Autonomy, recharge & battery life based on 25°C ambient

GENERAL
Input Receptacles

See rear panel drawings

Output Receptacles

See rear panel drawings

Display/Alarm

Front panel LED’s, audible alarms. See front panel layout

Interface (Rear Panel)

1 x RS232 & 1 x USB (fitted in option slot)

Software

Supplied bundled to support Windows 95, 98, ME, 2000, XP & NT

REPO (XTi 6000 only)

Remote emergency power off, must be fitted for unit to function. Connector on rear of unit. Remove
link to shut down output in AC mode or shut down unit in battery mode

ENVIRONMENTAL
Operating Temperature

0°C to +40°C

Storage Temperature

-15°C to +50°C

Operating Humidity

0-95% RH non-condensing

Operating Altitude

3000m without derating

Acoustic Noise

<45dBA at 1 metre

Ingress

IP20

EMC & SAFETY
Emissions

EN55022 level B

ESD Immunity

EN61000-4-2, level 3

Radiated Immunity

EN61000-4-3, level 2

EFT/Burst

EN61000-4-4, level 2

Surge

EN61000-4-5, level 3

Safety Approvals

EN50091-1-1, EN60240-1-1

Electrical Specification

XT Series
1.6-6kVA
True On-Line UPS

Features

Standalone Format

Isolation Transform (XT6000 only)

A400, RS232 & SNMP Adaptor Options

Front Panel LED Mimic

Green Mode Operation

Optional 10 Year Batteries