Powersolve JB200 Series User Manual
Ac-dc converters
www.powersolve.co.uk
Powersolve Electronics Ltd. 8A, Arnhem Road, Newbury, RG14 5RU. England
Tel:01635 521858 Fax: 01635 523771 Email: [email protected]
AC-DC Converters
JB200 Redundant Series
200 Watts
Single Output
Switching Power Supply
Features
•
Providing Peak Power of 600W within 500uS duty duration
•
Compact 1U Height & Power Density: 5.16 watts/cu in
•
Power factor corrected to EN61000-3-2 class A
•
Approved to UL CUL TUV CB and CE
•
AC input range auto-selectable
•
N+1 parallel redundancy
•
Optional Top Cover
Input Voltage:
90-132 / 180-264Vac, 47-63HZ auto selectable.
Input Current:
5/2.5A at 115/230VAC.
Inrush Current:
Max. 70A@230Vac & 35A@115Vac; cold start.
PFC:
Power factor correction to EN61000-3-2 class A (total parallel output power not exceeding 200W).
Transient Response:
Output voltage returns to within 1% in less than 2.5mS for a 50% load change, peak does not exceed 5%.
Overshoot:
Turn-on & off overshoot < 5% over nominal voltage.
Efficiency:
70% for 3.3V, 75% for 5V, 80% for 12V and 83% minimum for other outputs @ 230V and full load.
Turn On Delay:
1 second maximum at 120 VAC.
Hold Up Time:
20mS min. at120Vac & 80% of full load.
Adjustability:
Output user adjustable +/-5% minimum.
Input Fusing Protection:
One T5A/250V fuse inserted in primary.
Over-Voltage Protection:
Unit latches down when output exceeds 130% and recycle AC input to reset.
Over-Power Protection:
Fold back mode 110-135%; Auto-recovery.
Short-Circuit Protection:
Trip without damage and auto-recovery.
Over-Temperature Protection: Unit protected against excessive operating ambient of 85 °C, and automatic recovery.
Switching Frequency:
25KHZ fixed frequency.
Operating Temperature:
0 to 40 degrees C.
Storage Temperature:
-20 to 85 degrees C.
Operating Humidity:
5% to 90% RH, Non-condensing.
Storage Humidity:
5% to 95% RH, Non-condensing.
Vibration:
Frequency 5 to 50 Hz, acceleration +/-7.35 M/(SxS) on X,Y and Z Axis.
Remote On-Off:
Designated as REMO on the CN3. Requires a low signal to inhabit output; Hiccough mode.
Power Supply On:
Green LED designated as LED1 on the PCB.
Power Good:
Designated as PG on the CN3 will go high 100-500 mS after regulation and goes low 1mS before loss of regulation.
Fan Drive:
12VDC/300 mA is available to drive an external fan.
EMC Standards:
CISPR 22 / EN55022 class B, EN61000-3-2,3, EN61000-4-2,3,4,5,6,8,11, EN55024 CE Marked (LVD).
Safety Regulation:
Approved to UL60950-1, CSA C22.2 No. 60950- 1, TUV EN60950-1 and CB certificate available.
Leakage Current:
1.5mA @ 240Vac.
HI-POT Test:
1500 VAC input line to chassis (10mA DC cut off current);
Isolating 3000VAC primary to secondary windings;
Primary to core 1500VAC. All for 3 sec.
Grounding Test:
Apply 25 A from ground pin of the three prong plug to the far most earth. Max allowable resistance 0.1 ohm.
MTBF:
100000 Hrs (according to MIL-HBK-217F) at 30 degree C.
Cooling:
200W max. with 18.7cfm airflow or 150W max convection.
Enclosure:
6.8(L) x 3.8(W) x 1.5(H) inches; U-Chassis Type.
Weight:
Maximum weight is 600g.
Electrical Specification
Overall Size: 6.8(L) x 3.8(W) x 1.5(H)inches