VEGA VEGAPULS 61 (≥ 2.0.0 - ≥ 4.0.0) Foundation Fieldbus Approval according to LPR radio standard User Manual
Page 80
The function block "Input Selector" offers selection possibilities for up to four inputs and generates an
output signal according to the selection criteria. Typical input signals are AI blocks. Selection
possibilities are maximum, minimum, mean value, average value and first useful signal. Through
parameter combination, the block can be used as rotary switch or as preselection switch for the first
useful value. Switch information can be received by other input blocks or the user. Mean value
selection is also supported.
Fig. 58: Schematic presentation function block Input Selector
Function block Arithmetic
The function block "Arithmetic" allows the simple integration of usual metrological calculation
functions. The user can select the requested algortihm according to the name without known the
formula.
The following algorithms are available:
l
Flow compensation, linear
l
Flow compensation, square root
l
Flow compensation, approximate
l
BTU flow
l
Traditional Multiply Divide
l
Average
l
Traditional Summer
l
Fourth order polynomial
l
Simple HTG compensated level
80
VEGAPULS
61 • Approval according to LPR radio standard
11 Supplement
41716
-EN
-120301