VEGA VEGAPULS 61 (≥ 2.0.0 - ≥ 4.0.0) Foundation Fieldbus Approval according to LPR radio standard User Manual
Page 43
2
Edit the percentage value with [OK] and set the cursor to the
requested position with [->].
3
Set the requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
4
Enter the suitable distance value in m for the empty vessel (e.g.
distance from the sensor to the vessel bottom) corresponding to
the percentage value.
5
Save settings with [OK] and move with [ESC] and [->] to the max.
adjustment.
Proceed as follows:
1
Select with [->] the menu item max. adjustment and confirm with
[OK]
.
2
Prepare the percentage value for editing with [OK] and set the
cursor to the requested position with [->].
3
Set the requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
4
Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. Keep in mind that the max.
level must lie below the min. distance to the antenna edge.
5
Save settings with [OK]
Min. and max. measured values are saved in the sensor. The values
are displayed in the menu item "Peak values".
Setup/Max. adjustment
Diagnosis/Peak value
VEGAPULS
61 • Approval according to LPR radio standard
43