VEGA VEGAPULS 61 (≥ 2.0.0 - ≥ 4.0.0) Foundation Fieldbus Approval according to LPR radio standard User Manual

Page 43

background image

2

Edit the percentage value with [OK] and set the cursor to the
requested position with [->].

3

Set the requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.

4

Enter the suitable distance value in m for the empty vessel (e.g.
distance from the sensor to the vessel bottom) corresponding to
the percentage value.

5

Save settings with [OK] and move with [ESC] and [->] to the max.
adjustment.

Proceed as follows:

1

Select with [->] the menu item max. adjustment and confirm with
[OK]

.

2

Prepare the percentage value for editing with [OK] and set the
cursor to the requested position with [->].

3

Set the requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.

4

Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. Keep in mind that the max.
level must lie below the min. distance to the antenna edge.

5

Save settings with [OK]

Min. and max. measured values are saved in the sensor. The values
are displayed in the menu item "Peak values".

Setup/Max. adjustment

Diagnosis/Peak value

VEGAPULS

61 • Approval according to LPR radio standard

43