4 remove interferences – VEGA VEGAPULS 61 (≥ 2.0.0 - ≥ 4.0.0) Foundation Fieldbus Approval according to LPR radio standard User Manual

Page 58

background image

Code
Text mes-
sage

Cause

Rectification

M

503

Reliability too
low

l The echot/noise ratio is the

small for a reliable measu-
rement

l Check installation and pro-

cess conditions

l Clean the antenna
l Change polarisation direc-

tion

l Use instrument with higher

sensitivity

M

504

Error on an
device inter-
face

l Hardware defect

l Check connections
l Exchange of the electro-

nics

l Send instrument for repair

M

505

No echo avai-
lable

l Level echo can no longer

be detected

l Clean the antenna
l Use a more suitable an-

tenna/sensor

l Remove possible false

echoes

l Optimize sensor position

and orientation

9

.4 Remove interferences

The operator of the system is responsible for taking suitable measures
to rectify faults.

The first measures are:

l

Evaluation of fault messages via the indicating and adjustment
module

l

Checking the 4 … 20 mA signal

l

Treatment of measurement errors

Further comprehensive diagnosis possibilities are offered by a PC with
the software PACTware and suitable DTM.

In many case, the failure reasons can thus be determined and faults
rectified.

The below tables show typical examples of application-relevant
measurement errors with liquids. The measurement errors are
differentiated according to the following:

l

Constant level

l

Filling

l

Emptying

Reaction when malfunc-
tions occur

Procedure for fault rec-
tification

Treatment of measure-
ment errors with liquids

58

VEGAPULS

61 • Approval according to LPR radio standard

9 Diagnosis, Asset Management and service