are the normal call charges.
9
.5 Exchanging the electronics module
If the electronics module is defective, it can be replaced by the user.
In Ex applications only one instrument and one electronics module with
respective Ex approval may be used.
If there is no electronics module available on site, the electronics
module can be ordered through the agency serving you. The
electronics modules are adapted to the respective sensor and differ in
signal output or voltage supply.
The new electronics module must be loaded with the default settings
of the sensor. These are the options:
l
In the factory
l
Or on site by the user
In both cases, the serial number of the sensor is needed. The serial
numbers are stated on the type label of the instrument, on the inside of
the housing as well as on the delivery note.
When loading on site, first of all the order data must be downloaded
from the Internet (see operating instructions manual "Electronics
module").
9
.6 Software update
The following components are required to update the sensor software:
l
Sensor
l
Voltage supply
l
Interface adapter VEGACONNECT 4
l
PC with PACTware
l
Current sensor software as file
Caution:
Keep in mind that a software update can lead to expiry of the
approvals. You can find detailed information on our homepage www.
vega.com.
l
Go under "www.vega.com/downloads" to "Software"
l
Select under "plics sensors and instruments", "Firmware updates"
your instrument series and software version
l
Load the zip file via the right mouse key with "Save target as", for
example, on the desktop of your PC
l
Go with the right mouse key to the folder and select "Extract all"
l
Store the extracted files, for example on the desktop
Load sensor software to
PC
62
VEGAPULS
61 • Approval according to LPR radio standard
9 Diagnosis, Asset Management and service