5
.2 Connect
The voltage supply and signal output are connected via the spring-
loaded terminals in the housing.
The connection to the indicating and adjustment module or to the
interface adapter is carried out via contact pins in the housing.
Proceed as follows:
1
Unscrew the housing cover
2
If an indicating and adjustment module is installed, remove it by
turning it slightly to the left.
3
Loosen compression nut of the cable entry
4
Remove approx. 10 cm (4 in) of the cable mantle, strip approx.
1 cm (0.4 in) of insulation from the ends of the individual wires
5
Insert the cable into the sensor through the cable entry
Fig. 20: Connection steps 5 and 6
6
Insert the wire ends into the terminals according to the wiring plan
Information:
Solid cores as well as flexible cores with cable end sleeves are
inserted directly into the terminal openings. In case of flexible cores
without end sleeves, press the terminal head with a small screwdriver;
the terminal opening is freed. When the screwdriver is released, the
terminal closes again.
7
Check the hold of the wires in the terminals by lightly pulling on
them
8
Connect the screen to the internal ground terminal, connect the
outer ground terminal to potential equalisation
Connection technology
Connection procedure
VEGAPULS
61 • Approval according to LPR radio standard
27