VEGA MINITRAC 31 Profibus PA User Manual
Page 87
87
11 Supplement
MINITRAC 31 • Profibus PA
43836-EN-131119
Byte n
Byte n+1
Bit
7
VZ
Exponent
Bit
6
2
Bit
5
2
Bit
4
2
Bit
3
2
Bit
2
2
Bit
1
2
Bit
0
2
Bit
7
2
Bit
6
2
Bit
5
2
Bit
4
2
Bit
3
2
Bit
2
2
Bit
1
2
Bit
0
2
Sign
Bit
Significant
7
6
5
4
3
2
1
0
-1
-2
-3
-4
-5
-6
-7
Byte n+2
Byte n+3
Bit
7
2
Significant
Bit
6
2
Bit
5
2
Bit
4
2
Bit
3
2
Bit
2
2
Bit
1
2
Bit
0
2
Bit
7
2
Bit
6
2
Bit
5
2
Bit
4
2
Bit
3
2
Bit
2
2
Bit
1
2
Bit
0
2
Significant
-9
-10 -11 -12 -13 -14 -15 -16 -17 -18 -19 -20 -21 -22 -23
-8
Value = (-1)
VZ
2
(Exponent - 127)
(1 + Significant)
Fig. 27: Data format of the measured value
Coding of the status byte associated with the PA output value
You can find further information for the coding of the status byte in the Device Description 3.02 on
Status code
Description according to
Profibus standard
Fault description
0 x 24
bad
(F) Failure
0 x 3C
bad
(C) Function Check
0 x 78
uncertain
(S) Out of Spec
0 x A4
good
(M) Maintenance required
0 x A8
good
(M) Maintenance demanded
0 x 00
good
(G) Good
Mapping - User error codes
Priority
Description according to
Profibus standard
User Error Codes
NE-107 status
31
Hardware Failure
40, 41
FAILURE
30
Memory Failure
34, 35, 36, 37
FAILURE
29
Software Failure
80
FAILURE
28
Parameterization corrupt
72
FAILURE
27
Undefined 27
-
-
26
Undefined 26
-
-
25
Parameterization Error
16, 17, 25, 52, 53, 57, 66,
117, 120
FAILURE
24
Conflict in MGC
121, 122, 141
FAILURE
23
Communication Error in
MGC
8
FAILURE
22
MGC-Slave reports Error
38
FAILURE
21
Undefined 21
-
-
20
Undefined 20
-
-
19
Undefined 19
-
-
18
Detector Temperature
critical
125
OUT_OF_SPEC