VEGA MINITRAC 31 Profibus PA User Manual
Page 47

47
6 Set up with the display and adjustment module
MINITRAC 31 • Profibus PA
43836-EN-131119
In this menu item you can activate the relay output and determine its
function as well as the switching points.
When the output of the process values is set, you can choose be-
tween overfill and dry run protection.
The relay outputs of the sensor react accordingly.
The following reference values can be selected:
•
None - Relay operates as fail safe relay
•
Electronics temperature
•
Process value
"No" reference value means that the relay output operates as fail safe
relay.
Push the [->] button, to reach the relay settings.
Example for the adjustment of the process value
First of all select the requested mode (overfill or dry run protection).
Caution:
Independent of the selected reference value, the relay will deenergize
in case of failure.
With this menu item you safeguard the sensor parameters against
unauthorized or unintentional modifications.
This menu item is described in the operating instructions manual
"Display and adjustment module".
Display
With this parameter you can change the display language.
This parameter is described in the operating instructions manual
"Display and adjustment module".
With this parameter you can change the indication of the display.
Setup - Relay
Lock setup - adjustment
Display - Language
Display - Displayed value