6 Set up with the display and adjustment module

MINITRAC 31 • Profibus PA

43836-EN-131119

In the main menu point "Setup", the individual submenu points

should be selected one after the other and provided with the correct

parameters to ensure optimum adjustment of the measurement. The

procedure is described in the following.
Stick with the normal sequence of the menu items as closely as pos-

sible.
Setup
An address must be assigned to each Profibus PA instrument. Each

address may only be assigned once in the Profibus PA network. The

sensor is only recognized by the control system if the address is set

correctly.
When the instrument is shipped, address 126 is adjusted. This ad-

dress can be used for function test of the instrument and for con-

nection to a Profibus PA network. Then address must be changed to

integrate additional instruments.
The address setting is carried out either via:

The address selection switch in the electronics compartment of

the instrument (address setting via hardware)

The display and adjustment module (address setting via software)

PACTware/DTM (address setting via software)

The hardware addressing is effective if an address <126 is set

with the address selection switches on the electronics module of

MINITRAC 31. Software addressing thus has no effect - only the set

hardware address applies.

The software addressing is only effective if address 126 or higher is

adjusted on the instrument with the address selection switches.

If a hardware address was adjusted (< 126), then the instrument

signals that the hardware address is active.

Here you can assign a suitable measurement loop name. Push the

"OK" key to start the processing. With the "+" key you change the sign

and with the "->" key you jump to the next position.
You can enter names with max. 19 characters. The character set

comprises:

Capital letters from A … Z

Numbers from 0 … 9

Special characters + - / _ blanks

Setup - Sensor address

Hardware addressing

Software addressing

Setup - Measurement

loop name