6 Set up with the display and adjustment module

MINITRAC 31 • Profibus PA

43836-EN-131119

In menu item "Scaling" you define the scaling format on the display

and the scaling of the measured values for 0 % and 100 %.

Measured value min.

Measured value max.

To damp process-dependent measured value fluctuations, you can

set a time of 0 … 999 s in this menu item.

The default setting is a damping of 0 s.

In this menu item you can select which mode the sensor should oper-

ate in.
You can choose between overfill and dry run protection.
The relay outputs of the sensor react accordingly.
Overfill protection = the relay will deenergise (safe condition) when

the max. level is reached.
Dry run protection = the relay will deenergise (safe condition) when

the min. level is reached.
Make sure that you have selected the correct characteristics. See

menu item "Setup/Current output mode".

With this menu item you safeguard the sensor parameters against

unauthorized or unintentional modifications.

Setup - AI FB1 - Scaling

Setup - AI FB1 - Damping

Setup - Relay

Lock setup - adjustment