6 Set up with the display and adjustment module

MINITRAC 31 • Profibus PA

43836-EN-131119

Information:

In this operating instructions manual, the instrument-specific param-

eters are described. Further general parameters are described in the

operating instructions manual "Display and adjustment module".
Caution:

During the first setup or after an instrument reset the instrument starts

with preset standard values. These value are not suitable for your ap-

plication and must be replaced by real values.
Carry out a setup in the sequence described in the following.

The main menu is divided into five sections with the following func-

tions:

Setup: Settings, e.g. for measurement loop name, isotope, applica-

tion, background radiation, adjustment, signal output
Display: Settings, for example language, measured value display
Diagnosis: Information, for example, of device status, peak value,

simulation
Additional adjustments: Instrument unit, reset, date/time, copying

function
Info: Instrument name, hardware and software version, date of manu-

facture, instrument features

Check if the correct language is already set for the display. If not, you

can change the language in the menu item "Display/Language".

Start with the setup of MINITRAC 31.
In the main menu point "Setup", the individual submenu points

should be selected one after the other and provided with the correct

parameters to ensure optimum adjustment of the measurement. The

procedure is described in the following.
Stick with the normal sequence of the menu items as closely as pos-

sible.
Setup
An address must be assigned to each Profibus PA instrument. Each

address may only be assigned once in the Profibus PA network. The

sensor is only recognized by the control system if the address is set

correctly.
When the instrument is shipped, address 126 is adjusted. This ad-

dress can be used for function test of the instrument and for con-

Instrument start

Main menu

Procedure

Setup - Sensor address