6 parameter adjustment - x-ray alarm – VEGA MINITRAC 31 Profibus PA User Manual
Page 61
61
6 Set up with the display and adjustment module
MINITRAC 31 • Profibus PA
43836-EN-131119
•
Load parameter adjustment data from the sensor into the display
and adjustment module
•
Write parameter adjustment data from the display and adjustment
module into the sensor
This parameter is described in the operating instructions manual
"Display and adjustment module".
Info
In this menu you will find the following menu items:
•
Instrument name - shows instrument name and serial number
•
Instrument version - shows hardware and software version of the
instrument
•
Date of manufacture - shows calibration date and the date of the
last change
•
Profibus Ident Number - shows the Profibus ident number
•
Instrument features - shows further instrument features
These parameters are described in the operating instructions manual
"Display and adjustment module".
6.6 Parameter adjustment - X-ray alarm
X-ray radiation, for example, cause with weld joint tests can influence
your measured values unnoticeably. Hence it is importnat to recog-
nized interfering X-ray radiation.
The MINITRAC 31 recognizes the X-ray raditation and reacts from an
individually definable raditiation volume.
The level or density measuring instrument acts as Master and the
MINITRAC 31 operates as Slave.
First of all, define the function of the Slave instrument before you
define the Master instrument. The Master instrument can thus imme-
diately recognize the connected Slave.
For this purpose, the Slave instrument must be defined as "X-ray
alarm". Select under the menu item "Setup/Application" the function
"X-ray alarm".
You can set the address (MGC) on the Slave instrument at will. Only
the address "0 - 0" is reserved for the Master instrument.
Set the address setting (MGC) on the Master instrument to "0 - 0".
You have to enter the address of the Slave instrument in the list of
the Master instrument. This function is not possible in the display and
adjustment module. To do this you need PACTware with the respective
DTM.
The main menu is divided into five sections with the following func-
tions:
Info
X-ray alarm
Main menu