beautypg.com

7 diagnostics, 1 simulation, 2 error codes – VEGA VEGASCAN 850 User Manual

Page 90

background image

90

VEGASCAN 850

Diagnostics

7 Diagnostics

7.1 Simulation

For simulation of a certain filling, you can call
up the function "Simulation“ on the adjustment
module MINICOM, in the software program
VVO or on the signal conditioning instrument.

You simulate a vessel filling and thereby a
certain sensor current. Please note that con-
nected instruments, such as e.g. a PLC react
according to their adjustments and will prob-
ably activate alarms or system functions.

Simulation with VVO

If you start the simulation mode with the ad-
justment program VVO on the PC, the simu-
lated level is outputted until you quit the
simulation mode.

Simulation with MINICOM

If you start the simulation mode on the adjust-
ment module MINICOM, the sensor returns to
standard operating mode after one hour.

7.2 Error codes

Error codes

Removal

E013

No valid measured value

Message is displayed during the warm-up phase
- Sensor in the warm-up phase
- Loss of the useful echo
If the message remains, a false echo storage
(with the adjustment software on the PC - see
“Echo curve” under “Sensor optimisation”) must
be carried out together with a modification of
mounting location and orientation to achieve the
lowest possible false echo background.

E017

Adjustment span too small

Carry out a readjustment.
Make sure that the difference between
min. and max. adjustment is at least 10 mm.

E036

Sensor software does not run

Sensor requires new software (service).

Message appears during a software update.

E040

Hardware failure/Electronics defec-

Check all connection cables.

tive

Transducer defective.
Contact our service department.