Setup - Adjustment with the PC

Parameter adjustment 2

Linearisation

The relation between level and filling volume
is described with so-called linearisation
curves. If, in your vessel, there is a correla-
tion other than linear between level ("

Percent-

age value“ of the level) and the filling volume
(value of the filling volume), choose in the
menu window "

Conditioning“ the menu item

"

Instrument data/Parameter adjustment/Con-

ditioning“.

• Click in the menu window "

Conditioning“ to

the menu item

"Linearisation“.

The menu window "

Linearisation“, in which a

correlation between percentage value of the
level and the percentage value of the filling
volume is preadjusted.

Beside the two programmed linearisation
curves "

Horizontal cylindrical tank“ and

"

Spherical tank“ you can also enter "user

programmable curves“. Linear means there
is a linear correlation between level and vol-
ume.

User programmable linearisation curves

• Click to

"User programmable curve“ to

enter your own vessel geometry or a user
programmable filling curve.

• Click to

"Edit“.