Setup - Adjustment with the PC
In the menu "
Instrument data/Parameter ad-
justment/Conditioning/Linearisation“ you can
enter later, if necessary, a correlation be-
tween product distance and percent value of
volume other than linear (see later subitem
linearisation).
Scaling
• Click in the menu window "
Instrument data
parameter adjustment“ to "
Conditioning“.
The menu window "
Conditioning“ opens.
• Click to "
Scaling“.
In the menu "
Scaling“ you enter the actual
0 % and 100 % values of the parameter and
their unit. You thereby inform the sensor, e.g.
that at 0 % filling there are still 45 liters and at
100 % filling 1200 liters in the vessel. The
sensor display then shows with empty vessel
(0 %) 45 liters and with full vessel (100 %)
1200 liters.
As parameter you can choose
"dimension-
less (plain numbers), volume, mass, height
and distance“ and assign an appropriate
measuring unit (e.g. l, hl). The sensor display
then shows the measured value in the se-
lected parameter and unit.
• Save the adjustments in the menu "
Scaling“
by clicking
"OK.
The adjustments are now transferred to the
sensor and you are again in the menu win-
dow "
Conditioning“.
• Click in the menu window "
Conditioning“ to
"
Quit“.
• Click in the menu window "
Instrument data
parameter adjustment“ to "
Quit“.