Page 57: Fault rectification

background image

VEGADIF 34 … 51

57

20094-EN-030731

Diagnostics

6 Diagnostics

Maintenance

VEGADIF 34 … 51 differential pressure trans-
mitters are maintenance-free. Only the wetted
parts are subject to a certain amount of wear.
Therefore check regularly the condition of
these parts, particularly the diaphragms and
process seals. Note the service instructions
VEGADIF 34 … 51 differential pressure trans-
mitter.

Repair

If the measures for failure rectification are not
successful, return the affected instrument for
repair to VEGA. Please note the following:
• Attach information: application, medium,

failure description.

• Remove buildup, especially it is composed

of substances hazardous to health.

Fault rectification

Through self-monitoring, VEGADIF differential
pressure transmitters offer a high degree of
reliability. Within the framework of self-monitor-
ing, the signal circuit 4 … 20 mA is additionally
used for transmission of failure information. If a
failure is detected, the output current takes on
a value of 21.5 mA. Before removing VEGADIF
to look for faults, the following should be
checked:
- atmospheric pressure compensation (for

level measurements on open vessels)

- electrical components and connections

Checking the electrical components

1

+

2

-

3

4 ... 20 mA

+

-

~

+

V

mA

VEGADIF
terminals

Voltage

Current

External
energy source

Instructions for Ex applications

Deviating from the above arrangement, termi-
nal 1 and tag 1 are used only for short-term
connection to a certified, active floating (max.
value: 470 mW) or to any passive floating
measuring instrument. When connecting, the
regulations for wiring intrinsically safe circuits
(measuring instrument, supply and signal
circuit) must be noted.

External overvoltage arresters

(if present)
- check on interruption and short-circuit.

Voltage

- the terminal voltage on the differential pres-

sure transmitter must be at least
11.5 V DC.

- the supply voltage for the differential pres-

sure transmitter, provided by e.g. a
VEGAMET signal conditioning instrument,
must be approx. 25 V DC.

Current

Current value

Condition

3.8 … 20.6 mA

standard range of the output
current

21.5 mA

fault signal

0 mA

signal cable interrupted

< 3.6 mA

electronics or pressure sensor
element defective

> 21.6 mA

short-circuit in the signal cable,
electronics or pressure sensor
element defective