VEGA VEGAMET 614V User Manual
Page 7
VEGAMET 614V
7
Product description
Relay outputs
Number
2 operating relays, 1 fail safe relay
Contact
floating spdt
Contact material
AGSNO
2
, hard gold plated
Turn-on voltage
min. 10 mV DC
max. 250 V AC/DC
Switching current
min. 10 µA
max. 3 A AC, 1 A DC
Turn-on voltage
max. 750 VA
max. 18 W at U > 40 V DC
max. 40 W at U
≤
40 V DC
Min. switching hysteresis
(Low/High delta)
0.5 %
DISBUS output
Function
digital transmission for linking between signal
conditioning instruments and for connecting
digital indicating instruments
Connection cable
2-wire standard cable (screening
recommended)
max. cable length
1000 m
max. resistance per wire
15
Ω
Indicating elements
Clear text indication
LC display
- 4-lines, 6 digits each
- background lighting
Analogue indication
LED chain consisting of:
- 11 segments 0 % … 100 %
- indicates the actual value of the selected
measurement loop
LEDs in front plate
green: operating voltage on
red: fault signal (LED lights with deenergised
relay)
yellow: relay switching condition (standard
adjustment: LED lights with energised relay)
Adjustment elements
Front plate
6 keys for configuration and parameter setting
Upper housing side
rotary switch for adjustment of the instrument
address
on DISBUS (in mounted status covered by
plug-in socket)
Ambient conditions
Permissible ambient temperature
-20°C … +60°C
Storage and transport temperature
-40°C … +80°C
Electrical connection
Screw terminal
max. 1.5 mm
2