4 configuration of outputs, Settings in the „extended menu – VEGA VEGAMET 614V User Manual
Page 29

VEGAMET 614V
29
Settings in the „Extended menu“
7.4 Configuration of outputs
PC/DCS output and DIS output:
The PC/DCS signal as well as the DIS signal
are transmitted via the DISBUS. The PC/DCS
output delivers output signals from
VEGAMET to the interface converter
VEGACOM 557. This interface converter
transfers the signals from VEGAMET via
different standard protocols to connected
systems (DCS/DCS). In the menu items „DCS
1 to“ up to „DCS 7 to…“ the measurement
loop can be assigned or switched off. In the
menu items „PC/DCS relay status“ and „PC/
DCS input status“ it can be specified that the
relay mode is transmitted via the DISBUS. Up
to seven external indicating instruments
(VEGADIS 174) can be connected to
DISBUS. In the menu items „DIS 1 to…“ up to
„DIS 7 to–“ the measurement loop can be
coordinated or switched off.
The current, volt and relay outputs with
number 1 (current 1, Volt 1 and Rel. 1) are
assigned as factory setting to measurement
loop „TAG-No. 1“. If a second measurement
loop exists, as is the case when a sensor
with temperature output is connected, then
the outputs with number 2 are assigned to
measurement loop TAG-No. 2. All outputs can
be assigned individually to the other meas-
urement loop or switched off (----), i.e. the
switched off outputs do not access a meas-
urement loop.
A hold function or a reset of alarm functions
can be assigned to each operating relay. In
this case, the menu item „Input“ appears.
Here, the relay can be assigned to „Input 4“
(correction input). For a description of the
relay functions, see the following pages.
TAG 2
----
Config
inputs
Config
meas.
loop
Config
outputs
Config
current
output
Current
1 to
TAG -
No. 1
Current
2 to
TAG -
No. 2
Config
Volt
output
Config
relay
output
Config
PC/
DCS-
output
Config
VEGA-
DIS
DIS 1
to
TAG -
No. 1
DIS 7
to
----
PC/
DCS
meas.
values
DCS 1
to
TAG -
No. 1
DCS 7
to
----
PC/DCS
relay
status
off
PC/DCS
input
status
off
Confi-
gura-
tion
Param.
TAG-
No. 2
Fail
safe
relay
Rely
Stan-
dard
Ope-
rating
relay
Rel. 1
to
TAG -
No. 1
Rel. 2
to
TAG -
No. 2
TAG 1
----
TAG 2
----
TAG 1
----
----
----
TAG 2
----
Volt1
to
TAG -
No. 1
Volt2
to
TAG -
No. 2
TAG 1
----
TAG -
No. 1
%
xx,x
Param.
TAG-
No. 1