beautypg.com

6 conditioning – VEGA VEGAMET 614V User Manual

Page 31

background image

VEGAMET 614V

31

Settings in the „Extended menu“

7.6 Conditioning

The menu items „

Scaling

“ and „

Integration

time

“ correspond to the menu items in the

„reduced menu“ (see appropriate chapter).

The menu item „

Density…

“ is displayed as

an option when under „Configuration meas-
urement loop“ the appropriate sensor type
has been selected. The density value must,
before adjustment with medium, be so ad-
justed that it corresponds to the value of the
medium (water has a density of 1.0 kg/dm

3

).

The following linearisation curves are avail-
able:
- linear (factory setting)
- horiz. cylindrical tank
- spherical tank
- Lin-curve 1
- Lin-curve 2
- Lin-curve 3

Lin-curves 1 … 3 can be edited by the
user (see appropriate chapter).

After scaling or linearisation, the required
output must be assigned to the scaled or
linearised value (menu item "prop. to..." and
"Unit...") in the menu range "Parameter adjust-
ment outputs".

Under

Meas. value limitation,

you can ex-

clude negative values.

Failure mode Standard

means that at a sensor current of 3.6 mA or
21 mA, the fail safe relay responds.

Failure mode >110%

also causes a fault signal if a meas. value of
more than 110 % or less than -10 % is
reached.

Param.
TAG-
No. 2

like TAG-No. 1

Param.
TAG-
No. 1

Adjust-
ment

Signal
condi-
tioning

TAG -
No. 1
%
xx,x

Scaling

Lin.
curve

linear

0%
corres-
ponds

0

100%
corres-
ponds

1000

Integr
ation
time s

0

Den-
sity in
Kg/dm

3

1,000

Meas.
value
limita-
tion

Deci-
mal
point

888,8

prop.
to

unde-
fined

Unit

– –

nega-
tive
values

yes

Failure
mode

Stan
dard

cylindrical tank…

>110%