23

Settings in the „Reduced menu“

6.6 Integration time

Percent
Pressure
Mass

prop.
to

Height

Unit

m

dm
cm
….

TAG -
No. 1

m

2,341

TAG-
No. 1
%
xx,x

Param.
TAG-
No. 1

Ad-
just-
ment

Sig-
nal
condi-
tioning

Scal-
ing

Integr
ation
time s

0

Meas.
value
indication

If the integration time is set to 0 s (factory
setting), each quick change of the product
surface (e.g. waves) will be immediately
detected and interpreted as level change. All
output values of VEGAMET will follow the
wave movements. To avoid this, the integra-
tion time can be increased (max.
600 s are possible with VEGAMET). The
higher the time setting, the slower the meas-
ured value display reacts.

Scaling example

You have a raised tank and you want the
level to be indicated in meters with three
places after the decimal point.

Enter the number 1500 (with keys
[+], [–] and [OK]) in this menu item.
This corresponds to the level at 0 %
(if you want to have a lower resolution

of the meas. value indication, you can also
enter 150 or 15).

Enter the number 4500 (with keys
[+], [–] and [OK]) in this menu item.
This corresponds to the level at
100 %.

Adjust the decimal point as shown
(with keys [+], [–] and [OK]).

Choose the term „Height“ in this
menu item (with keys [+], [–] and
[OK]).

If you have chosen „Height“ in the
previous menu item, you get a choice
of several units (mm, dm, cm, m,
yard…). Choose m (with the keys
[+], [–] and [OK]).

You can now see the scaled value in
the measured value display.

0%
corres-
ponds

1500

100%
corres-
ponds

4500

Deci-
mal
point

8,888

100 %

0 %

h=1.5 m

h=4.5 m

2.341 m