47
Error code
Meaning
Diagnosis
E022
Scaling span too big.
E027
Actual measured value is less than -10 %.
E28
Actual measured value is more than 110 %.
E031
Same DISBUS address. At least one other instrument with the same DISBUS
address is connected to the DISBUS. Please check the DISBUS address.
E032
Instrument address 0. Instrument address 0 is adjusted on VEGAMET. With this
address VEGAMET does not participate in the DISBUS communication, even if
the DISBUS is wired. If necessary, modify the instrument address.
E034
Instrument error. A serious error was detected in the instrument (possibly de-
fective EEPROM). Disconnect voltage and then connect again (cold start). If the
error is not eliminated, please contact your VEGA agency.
E035
Instrument error. A serious error was detected in the instrument (check sum
error in EPROM). Disconnect voltage and then connect again (cold start). If the
error is not eliminated, please contact your VEGA agency.
E050
Remote VEGAMET not found. The VEGAMET from which a measured value is
expected cannot be found.
Reasons:
- the remote VEGAMET is not connected
- no VEGAMET with this instrument address connected
- line break (DISBUS)
- short circuit (DISBUS)
- the remote VEGAMET is defective
- interfered communication (DISBUS)
Also possible
- failure on the DISBUS transmitter/receiver part of VEGAMET
Please check the instrument address on both VEGAMETs, the connection ca-
ble, the remote VEGAMET and, if necessary, this VEGAMET.