3 electrical connection, 1 connection instructions, 2 wiring plan – VEGA VEGAMET 614V User Manual
Page 12
12
VEGAMET 614V
3.2 Wiring plan
Fail
safe
relay
Level
relay 1
Level
relay 2
Power supply
VBUS
sensor
Current
output 1
The connections „9, 10, 15, 16, 17 and 18“ can be
connected with the supplied jumpers to neighbouring
series 600 signal conditioning instruments.
Electrical connection
3 Electrical connection
3.1 Connection instructions
Note the following instructions for electrical
connection:
- The connection must be made acc. to the
local installation standards (e.g. in Ger-
many acc. to the VDE-regulations).
- The wiring between VEGAMET 614 V and
sensor can be made with standard two-
wire cable.
- If strong electromagnetic interferences are
expected, we recommend the use of
screened cable. The screening must be
earthed on both ends.
- The line resistances stated in the technical
data must not be exceeded.
- If overvoltages are expected, we recom-
mend a sensor electronics with integrated
overvoltage protection or the installation of
VEGA overvoltage arresters.
Connection instructions for Ex
approved applications
When wiring between VEGAMET 614V Ex
and an explosion protected sensor, the in-
stallation rules, in Germany acc. to VDE 165
and the EC type approval certificate must be
observed. The official documents are sup-
plied with the respective instrument.
Current
output 2
Ex version
Before connecting Ex certified instruments,
please note the instructions in the attached
official documents as well as the valid installa-
tion regulations. Make sure that the Ex sepa-
rating chamber is plugged in on the left
instrument side before setup (see illustration
Coding).