Relay outputs, Settings in the „extended menu – VEGA VEGAMET 614V User Manual
Page 33

VEGAMET 614V
33
Settings in the „Extended menu“
Relay outputs
In the menu item „
prop. to
“, you choose a
parameter that the relay will react to. You can
choose between percent and volume („prop.
to volume“ is useful when under „Conditioning
- Linearisation curves“, for example a spheri-
cal tank or a user-programmable lin. curve is
selected). In the next menu item you can
select the suitable
Unit
. In the menu item
„
Mode
“ the mode of the relay can be se-
lected. The individual relay modes are de-
scribed on the following pages.
If mode „Tendency rising“ or „Tendency fall-
ing“ is selected, the menu items „Deviation“,
„Dev. per time“, „Cycle time“ and „Number of
cycles“ appear.
With all other modes, the menu items „Low“
and „High“ appear. There you can determine
the switching points for the relay.
The menu item „
Failure mode
“ always ap-
pears. „Failure mode off“ causes the relay to
deenergise when a failure (e.g. sensor
shortcircuit) occurs. „Failure mode hold“
causes the actual relay status to be main-
tained when a failure occurs.
Under „Add’l functions“ you can adjust a
switch on delay (t on) and a switch off delay
(t off) of the relay of max. 600 s (with the relay
modes „Tendency rising“ or „Tendency fall-
ing“, no switching delay can be set).
Param.
TAG-
No. 2
like TAG-No. 1
Param.
TAG-
No. 1
TAG -
No. 1
%
xx,x
Adjust-
ment
Signal
condi-
tioning
Out-
puts
Cur-
rent
out-
puts
Volt
outputs
Relay
outputs
Relay
output
1
Relay
output
2
prop.
to
Per-
cent
Unit
0,0%
Mode
Over-
fill
protec
Low
%
0,0
Failure
mode
off
Add’l
func-
tions
Cycle
time
s
1
Number
of
cycles
10
like relay output 1
High
%
100,0
Devia-
tion
s
1,0
De-
viation
per
time
Switch-
ing
delay
t off
s
0
Volume
Height
Pressure
Dry run protec.
Switching window on
Switching window off
Tendency rising
Tendency falling
0,00 %
Tare %
hold
t on
s
0