VEGA VEGASON 71 - 1 … 75 - 1 User Manual
Page 51
Supplement
71 - 1 … 75 - 1
51
Error codes
Problems during measurement or faulty adjust-
ments during the programming are indicated on the
display with a fault signal.
Fault signals are made in the measured value
mode with channel specific indication via the
respective display.
Acc. to the table below, fault signals can cause the
fail safe relay to de-energize and the failure LEDs
light.
The current outputs as well as the switching relays
react channel specific acc. to the table below or
their parameter adjustment in mode 93.
After removing the failure (e.g. repair of a line
break) the fault signal extinguishes automatically.
Example of a fault signal:
1
E 3 . 0 4
Fault in channel: line break /
temperature sensor defect
= coding of the sensor
= error class
= E = Error
Error
E3.04
-
is undelayed with the switch on,
-
is indicated during operation after
approx. 15 secs.
error
error
preset
fail safe
relay output /
code
meaning
mode 1 - 24
relay / -LED
current output
E2.01
signal- / noise
= 0
distance < 1 dB
acc. to parameter adjustment
in mode 93
= 1
E2.02
echo in dead band
no
modification corresponds to
E2.03
postoscillation
influence
the value for 100 %
> 1,8 m
E3.01
data loss in the
no
E3.02
data memory
influence
no modification
E3.03
E3.04
line break /
= 0
temperature
acc. to parameter adjustment
sensor defect
in mode 93
= 1
ERR
parameter range
no
exceeded by
influence
no modification
adjustment