VEGA VEGASON 71 - 1 … 75 - 1 User Manual
Page 16
Start-up
16
71 - 1 … 75 - 1
Mode listing 0
Function
Mode-no.
Mode description
Parameter
Page
(
= factory preset)
0 - 00
Software version ........................................
e.g.
16.93
0 - 01
…
09
not used .....................................................
– – – –
Adjustment
0 - 10
Selection of adjustment procedure
channel 1
- in m without level change .......................
1
- per cent correction ..................................
2
- in % with level change ............................
3
0 - 11
Empty adjustment
- distance in m ...........................................
sensor specific
p. 19
- level in % ................................................
0.0
…
80.0
0 - 12
Full adjustment
- distance in m ...........................................
sensor specific
- level in % ................................................
100.0
…
20.0
Display
Multiplier
function
0 - 13
- related to 0 % .........................................
0000
…
9999
0 - 14
- related to 100 % .....................................
0000
…
1000
…
9999
0 - 15
Measuring unit
- level percentage in m .............................
1
p. 26
- level percentage in % .............................
2
- volume percentage (scaled) ...................
3
0 - 16
Decimal point ...........................................
0.000
…
000.0
…
0000
0 - 17
Integration time ........................................
0
…
900
Lineari-
0 - 18
Linearization curves
zation
- linear ......................................................
1
- cylindrical tank .......................................
2
- not used .................................................
3
p. 21
- individually programmable curve 4 .........
4
- individually programmable curve 5 ........
5
- individually programmable curve 6 .........
6
0 - 19
…
39
not used .....................................................
– – – –
Display
0 - 40
Display coordination
- level indication ........................................
1
- not used .................................................
2
- tendency determination (cm / min.) .......
3
0 - 41
a.
42
not used .....................................................
– – – –
general parameters