VEGA VEGASON 71 - 1 … 75 - 1 User Manual
Page 46
Adaption to filling and emptying speed
Rate of product level change
MODE 1 - 19
The rate of product level change is factory set by
VEGA within the adjustment range
-
0.01 … 11 cm / sec. with
-
4.00 cm / sec.
This adjustment should only be changed if this
seems useful in case the actual rate of product
level change exceeds the standard value.
Programming example
Change to 0,50 cm / sec. .........................................
• select mode 1 - 19 in MODEFIELD
• program 0.50 in PARAMETER FIELD
• then store with STO-button
Conversion schedule .............................................
cm / sec.
m / hours
Adjustment range ........
0,01
0,36
0,05
1,8
0,1
3,6
0,5
18,0
1,0
36,0
2,0
72,0
4,0
144,0
6,8
216,0
8,0
288,0
10,0
360,0
Storage of a false echo profile
46
71 - 1 … 75 - 1
Profile interpolation
MODE 1 - 18
With the function "false echo learn" gaps can exist
between the gated out false echoes.
With the activation of the profile interpolation, gaps,
smaller 3 m will be closed.
Build-up around struts, weldment joints etc. caused
after the time cycle, generate additional false
echoes.
Demonstration as comparison
Additional false echoes
by build-up
Programming example ..........................................
• select mode 1 - 18 in MODEFIELD
• program with figure 1 the profile interpolation in
PARAMETER FIELD
• then store with STO-button
Profile interpolation ..........................................
off ..............
on