Adjustment

71 - 1 … 75 - 1

19

Selection of adjustment procedure

The type of empty adjustment (mode 11) and full
adjustment (mode 12) is determined with the para-
meter adjustment of this mode.

The type of adjustment depends on the local condi-
tions.

Mode description

Mode 10 = 1

means adjustment in m without product level change, i.e.
- with the adjustment procedure the distances in m determined from the vessel drawings

are programmed relating to the levels 0 % and 100 %

- level is not important.

Mode 10 = 3

means adjustment in % with product level change, i.e.
- with this adjustment procedure the levels are programmed in % and the respective

measured distance (sensor … level) is calculated automatically

- product level change is needed.

Programming example

Change of mode 10 = 3 of mode 10 = 1 ..................

• select mode 0 - 10 in MODEFIELD
• program figure 1 in PARAMETER FIELD
• then store with STO-button

Demonstration

Mode 10 = 1

Mode 10 = 3

Min. distance
^ 100 %

partly filling
= e.g. 75 %

partly emptying
= e.g. 25 %

Max. distance
^ 0 %

MODE 0 - 10