Adaption to the product
42
71 - 1 … 75 - 1
Product type
MODE 1 - 09
The product type together with the vessel geometry
can generate different reflections and therefore
multiple echoes.
The available product type can be selected in this
mode. With this selection the data of the factory
preset of mode 1 - 10 and 1 - 11 can be activated.
The echo amplification is reduced or adapted after
the measuring window.
Programming example:
Change of liquids to solids .......................................
• select mode 1 - 09 in MODEFIELD
• program figure 0 in PARAMETER FIELD
• then store with STO-button
Product type ................................
Mode 1 - 09 = 1 = liquids
Mode 1 - 09 = 0 = solids
Liquid
solid
vessel geometry
solid features
- flat vessel top
- particle size > 10 mm
- dished vessel top
- angle of repose 0
°
Liquid
MODE 1 - 10
The vessel geometries of tank ceilings generate
characteristic multiple echoes.
They can be suppressed by adaption. A flat ceiling
is programmed as factory preset.
Features:
Mode 10 = 1
flat vessel tank .............................
= weak tendency to multiple echoes
= 0
dished vessel top .........................
= strong tendency to multiple echoes
(parabolic effects in the top area of tank)
Programming example:
Change of flat to dished vessel top ...........................
• select mode 1 - 10 in MODEFIELD
• program figure 0 in PARAMETER FIELD
• then store with STO-button
Adaption to the vessel geometry