INSTALLATION GUIDE
TROUBLESHOOTING
Problem
Solution
Status LED does not blink
Check fuses and voltage connections. Status
LED should blink regardless of CTs or output
connections.
Readings seem highly
inaccurate.
• Check that each CT is installed on the conductor
with the corresponding color voltage input
lead attached. In most cases, incorrect wiring
will cause the STATUS LED to blink RED (slowly).
However, a power factor lower than 0.5 could
cause the LED to blink this way, even if the unit is
installed properly.
• It does not matter which side of the CT faces
towards the load.
• If current is below 7% of full scale maximum
for the CT, use a smaller CT or wrap each wire
through the CT multiple times
• If using the single-phase H8042, use an amp-
clamp to ensure that all three phases are passing
the same approximate current. If phases are
unbalanced, try the H8043/H8044 models.
Meter goes offline when load
is switched off.
Voltage leads must be connected on the Line
side of the conductor. The power meter cannot
communicate without voltage.
Status LED blinks red.
• If the LED blinks quickly (i.e., about 5 blinks in
two seconds), then use a higher rated CT.
• If the LED blinks slowly (i.e., about 1 blink in
two seconds) the CTs are not installed on the
correct conductors, or the power factor is less
than 0.5. The meter can accurately measure
these low PFs, but few loads operate normally at
such a low power factor.
NOTES
1. DO NOT GROUND THE SHIELD INSIDE THE ELECTRICAL PANEL. All wires, including
the shield should be insulated to prevent accidental contact to high voltage
conductors.
2. The cable should be mechanically secured where it enters the electrical panel.
3. The cable should be shielded twisted pair wire BELDEN 1120A or similar.
WARNING: After wiring the cable, remove all scraps of
wire or foil shield from the electrical panel. This could
be DANGEROUS if wire scraps come into contact with high
voltage wires!
MAXIMUM READINGS
Model
3Ø Power (kW)
1Ø Power (kW)
H8041-0100-2
36.03
24.00
H8041-0300-2
108.1
72.00
H8041-0400-3
144.1
96.00
H8041-0800-3
288.2
192.0
H8041-0800-4
288.2
192.0
H8041-1600-4
576.4
384.0
H8041-2400-4
864.6
576.0
H8042-0100-2
83.14
55.43
H8042-0300-2
249.4
166.3
H8042-0400-3
332.6
221.7
H8042-0800-3
665.1
443.4
H8042-0800-4
665.1
443.4
H8042-1600-4
1330
886.7
H8042-2400-4
1995
1330
H8043-0100-2
36.03
36.03
H8043-0300-2
108.1
108.1
H8043-0400-3
144.1
144.1
H8043-0800-3
288.2
288.2
H8043-0800-4
288.2
288.2
H8043-1600-4
576.4
576.4
H8043-2400-4
864.6
864.6
H8044-0100-2
83.14
83.14
H8044-0300-2
249.4
249.4
H8044-0400-3
332.6
332.6
H8044-0800-3
665.1
665.1
H8044-0800-4
665.1
665.1
H8044-1600-4
1330
1330
H8044-2400-4
1995
1995