INSTALLATION GUIDE
WIRING
Typical 208/480 VAC 3Ø, 3- or 4-Wire Installation
Typical 240/120 VAC 1Ø, 3-Wire Installation
Typical 277 VAC 1Ø, 2-Wire Installation
4-20mA Output
4-20mA OUTPUT LINE
Model 8043/44
Model 8041/42 (Use on balanced loads only)
120V
120V
Black
Red
Yellow
Neutral
NOTE: Multiply output by
3 for proper kW indication
Model 8043
Model 8041
NOTE: Multiply output by
2 for proper kW indication
120
Neutral
120
4-20mA OUTPUT LINE
277V
Black
Red
Yellow
Neutral
Neutral
277
4-20mA OUTPUT LINE
Model 8044
NOTE: Multiply output by
2 for proper kW indication
Model 8042
4-20mA OUTPUT LINE
277V
Black
Red
Yellow
Neutral
NOTE: Wires are crossed through
the CT, each entering from
the opposite direction. This
arrangement does not require
multiplying the output data.
Model 8042
Alternative 277 VAC 1Ø, 2-Wire Installation