Measuring AC Voltage
WARNING!
Do not attempt to make a voltage measurement of more than
600V or of a voltage level that is unknown. Make sure the tem-
perature probe is NOT plugged in during this test.
Instrument set-up:
FUNC.
BLACK RED
MIN
MAX
TEST LEAD TEST LEAD
READING
READING
COM
V/
Ω
0.1mV
600V
Measurement Procedure:
1.
Disconnect power to circuit to be measured.
2.
Plug black test lead into the COM input jack.
3
Plug red test lead into the V/
Ω
input jack.
4.
Set rotary switch to the V range.
5.
Connect test leads to circuit to be measured.
6.
Reconnect power to circuit to be measured.
7.
Read the voltage on the 275.
Optional Modes
(See Other Features Section)
•
D-H:
Freezes the reading on the LCD.
•
MAX/MIN:
Records minimum and maximum measurements.
•
P-H:
Displays peak voltage.
2. Step by Step Procedures:
Measuring DC Voltage
WARNING!
Do not attempt to make a voltage measurement of more
than 600V or of a voltage level that is unknown. Make sure
the temperature probe is NOT plugged in during this test.
Instrument set-up:
FUNC.
BLACK RED
MIN
MAXI
TEST LEAD TEST LEAD
READING
READING
COM
V/
Ω
0.1mV
600V
Measurement Procedure:
1.
Disconnect power to circuit to be measured.
2.
Plug black test lead into the COM input jack.
3
Plug red test lead into the V/
Ω
input jack.
4.
Set rotary switch to the V range.
5.
Connect test leads to circuit to be measured.
6.
Reconnect power to circuit to be measured.
7.
Read the voltage on the 275.
Optional Modes
(See Other Features Section)
•
D-H:
Freezes the reading on the LCD.
•
MAX/MIN:
Records minimum a.
•
P-H:
Displays peak voltage.
15
14