beautypg.com

Veris Industries VT7300 SERIES Install User Manual

Page 7

background image

7

Schematic Wiring

Settings

4 pipe system cooling and heating: VT7300C5x00(x) & VT7305C5x00(x) On / Off N.C. actuators

Mandatory

Pipe no = 4 pipes

CntrltTyp = On/Off

Fan Menu = 0 (L-M-H)

FL time = as per actuator

SeqOpera = 4 Cool/Heat

4 pipe system cooling and heating: VT7300C5x00(x) & VT7305C5x00(x) Floating actuators

Mandatory

Pipe no = 4 pipes

CntrltTyp = Floating

Fan Menu = 0 (L-M-H)

FL time = as per actuator

SeqOpera = 4 Cool/Heat

4 pipe system cooling and heating: VT7300F5x00(x) & VT7305F5x00(x) Analog actuators

Mandatory

Pipe no = 4 pipes

Fan Menu = 0 (L-M-H)

RA/DA = as per actuator

SeqOpera = 4 Cool/Heat

2 pipe system cooling or heating with reheat: VT7300C5x00(x) & VT7305C5x00(x) Floating actuator

Mandatory

Pipe no = 2 pipes

CntrltTyp = Floating

Fan Menu = 0 (L-M-H)

FL time = as per actuator

SeqOpera = 2 Cool/Reheat

UI3 = COS

Normally Closed On/Off

Valve Cooling and Heating

Room Temperature
Control Thermostat

3 Speed fan

Modulating Floating

Valve Cooling and Heating

Room Temperature
Control Thermostat

3 Speed fan

24 V~ Com

24 V~ Hot

BO2 Close

Fan-L

Fan-M

Fan-H

High

Med

Low

24 Vac fan relays

Cooling

Heating

BO4 Close

24 V~ Com

24 V~ Hot

BO1 Open

BO2 Close

Fan-L

Fan-M

Fan-H

High

Med

Low

24 Vac fan relays

Cooling

Heating

BO3 Open

BO4 Close

Modulating Analog

Valve Cooling and Heating

Room Temperature
Control Thermostat

3 Speed fan

24 V~ Com

24 V~ Hot

AO1

AO2

Fan-L

Fan-M

Fan-H

High

Med

Low

24 Vac fan relays

Cooling

Heating

0 t o 10

Vd c

0 t o 10

Vd c

Modulating Floating

Valve Cooling and/or Heating

Room Temperature
Control Thermostat

3 Speed fan

Electric
Reheat

Optional supply water

temperature sensor

UI3 COS

24 V~ Com

24 V~ Hot

BO1 Open

BO2 Close

Fan-L

Fan-M

Fan-H

High

Med

Low

24 Vac fan relays

BO5

BO5