Veris Industries VT7300 SERIES Install User Manual
Page 12

12
Configuration parameters
Default value
Significance and adjustments
PswrdSet
Configuration parameters menu
access password
Default value = 0
Range is: 0 to 1000
This parameter sets a protective access password to prevent unauthorized access
to the configuration menu parameters. A default value of “0” will not prompt a
password or lock the access to the configuration menu.
Range is: 0 to 1000
Com Addr
Thermostat networking address
Default value = 254
Range is: 0 to 254
Conditional parameter to BACnet MS-TP models (VT73xxX5x00B)
Conditional parameter to Wireless models (VT73xxX5x00W)
•
For BACnet MS-TP models valid range to use is from 1 to 127. Default value of
254 disables BACnet communication for the thermostat.
•
For wireless models valid range is 0 to 254 with a maximum of 30 thermostat
per VWG
PAN ID
Personal Area Network
Identification
Default value = 0
Range is: 0 to 500
Conditional parameter to Wireless models (VT73xxX5x00W)
This parameter will only appear when a wireless network adapter is present. If the
thermostat is installed as a stand-alone unit or with a BACnet or Echelon adapter,
this parameter will not be used or displayed
This parameter (Personal Area Network Identification) is used to link specific
thermostats to a single specific Viconics wireless gateway ( VWG ) For every
thermostat reporting to a gateway ( maximum of 30 thermostats per gateway ), be
sure you set the SAME PAN ID value both at the gateway and the thermostat(s).
The default value of 0 is NOT a valid PAN ID. The valid range of available PAN ID
is from 1 to 500
Channel
Channel selection
Default value = 10
Range is: 10 to 26
Conditional parameter to Wireless models (VT73xxX5x00W)
This parameter will only appear when a wireless network adapter is present. If the
thermostat is installed as a stand-alone unit or with a BACnet or Echelon adapter,
this parameter will not be used or displayed
This parameter (Channel) is used to link specific thermostats to specific Viconics
wireless gateway(s) ( VWG ) For every thermostat reporting to a gateway (
maximum of 30 thermostats per gateway ), be sure you set the SAME channel
value both at the gateway and the thermostat(s).
Viconics recommends using only the 2 last channels ( 25-2575MHz and 26-
2580MHz )
The default value of 10 is NOT a valid channel. The valid range of available
channel is from 11 to 26
Get From
Thermostat Get From another
device configuration utility
Default value = 0
Range is: 0 to 254
Conditional parameter to Wireless models (VT73xxX5x00W)
This parameter / function is not currently supported by the wireless
thermostats.