Veris Industries PX SERIES Install User Manual
Px series, Notice, Digital pressure transducer dry media

Z205213-0D
PAGE 1
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
07122
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
EnvironmEntal SEnSorS
inStallation GUiDE
Digital Pressure Transducer
Dry Media
Installer’s Specifications
Media Compatibility
Dry air or inert gas
Input Power
12-30VDC, or 24VAC nominal; 2-wire: 20mA max.; 3-wire: 30mA max.
Output
Field-selectable: 2-wire, loop-powered 4-20mA
(DC
only, clipped and capped), or 3-wire 0-5V/0-10V*
Pressure Ranges:
PX: 01
Unidirectional: 0.1/0.25/0.5/1.0” W.C. F.S., switch selectable
Bidirectional: ±0.1/±0.25/±0.5/±1.0” W.C. F.S., switch selectable
Unidirectional:
25 Pa/50 Pa/100 Pa/250 Pa, F.S., switch selectable
Bidirectional: ±25 Pa/±50 Pa/±100 Pa/±250 Pa, F.S., switch selectable
PX: 02
Unidirectional: 1.0/2.5/5.0/10” W.C. F.S., switch selectable
Bidirectional: ±1.0/±2.5/±5.0/±10” W.C. F.S., switch selectable
Unidirectional: 0.250 kPa/0.500 kPa/1.000 kPa/2.500 kPa, F.S., switch selectable
Bidirectional: ±0.250 kPa/±0.500kPa/±1.000 kPa/±2.500 kPa, F.S., switch selectable
PXU: 05
Unidirectional: 0.1/0.25/0.5/1.0/2.5/5/10” W.C. F.S., switch selectable
Bidirectional:
±0.1/0.25/0.5/1.0/2.5/5/10” W.C. F.S., switch selectable
Unidirectional:
25Pa/50Pa/100Pa/250Pa/0.5kPa/1kPa/2.5kPa F.S., switch selectable
Bidirectional: ±25Pa/50Pa/100Pa/250Pa/0.5kPa/1kPa/2.5kPa F.S., switch selectable
Response Time
Standard: T95 in 20 sec, Fast: T95 in 2 sec, jumper selectable
Mode
Unidirectional or bidirectional, jumper selectable
Display (option)
Signed 3-1/2 digit LCD, indicates pressure, overrange indicator
Proof Pressure
3 psid (20.6kPa)
Burst Pressure
5 psid (34.5kPa)
Accuracy
±1% F.S. of selected range (combined linearity and hysteresis)
Temperature Effect
1” (250Pa) models: 0.05%/°C; 10” (2.5kPa) models: 0.01%/°C
(Relative to 25°C) 0° to 50°C (32° to 122°F)
Zero Drift (1-year)
1” (250Pa) models: 2.0% max.; 10” (2.5kPa) models: 0.5% max.
Zero Adjust
Pushbutton auto-zero and digital input (2-pos terminal block)
Operating Environment
0°- 60°C (32° to 140°F); 0 to 90% RH non-condensing
Fittings
Brass barb; 0.24” (6.1mm) o.d.
Physical
UL 94 V-O Fire Retardant ABS
EMC Conformance: EN 61000-6-3:2007 and A1:2011 Class B, EN 61000-6-1:2007
EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor
with proper surge protection (EN 61000-6-1:2007 specification requirements).
* Minimum input voltage for 4-20 mA operation: 250 Ω loop = 13 VDC; 500 Ω loop = 19 VDC
PX SerieS
PX SerieS
Dimensions
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
ProDuct iDentification
quick install
1. Plan the installation. Panel or duct mount?
2. For duct mounting, thread the probe into the rear of the device housing.
3. Configure the internal tubing for the selected installation method.
4. Mount the housing vertically.
5. Attach pilot tubing.
Enclosure
D = Duct
P = Panel
Local Display
L = LCD Display
X = No Display
NIST
N = NIST
X = None
Response
S = Selectable
F = Selectable
Range
01 = 0-1"W.C./0-250Pa
02 = 0-10"W.C./0-2.500kPa
PX
Local Display
L = LCD Display
X = No Display
NIST
N = NIST
X = None
Response
= Selectable
Range
= 0-10”/0-2.500kPa
PXU
05
S
Z103591-0A
Differential Pressure
Transmitter
Inch H2O
4.5"
(114 mm)
8.0"
(202 mm)
2.2"
(55 mm)
3.3"