Page 7

background image

Z204062-0F

PAGE 7

©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

02122

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

H8186-CB

INSTALLATIoN GUIDe

bacnet descriPtions

BACnet Object

Description

Description Field

Units

Device Object

This device

Veris H81xx Energy Meter

with H8186-CB BACnet

Communications Board

N/A

Analog Value Object 1

Accumulated Energy

kWh_Total

kWh

Analog Value Object 2

Device Instance

Device_Instance

N/A

Analog Input Object 1

Total Real Power

kW_Total

kW

Analog Input Object 2

Total Reactive Power

kVAR_Total

kW

Analog Input Object 3

Total Apparent Power

kVA_Total

kW

Analog Input Object 4

Total Power Factor

PF_Total

Unitless

Analog Input Object 5

Average Line-Line Voltage

Volts_LL_Avg

Volts

Analog Input Object 6

Average Line-Nuetral Voltage Volts_LN_Avg

Volts

Analog Input Object 7

Average Current

Current_Avg

Amps

Analog Input Object 8

Real Power: Phase A

kW_A

kW

Analog Input Object 9

Real Power: Phase B

kW_B

kW

Analog Input Object 10

Real Power: Phase C

kW_C

kW

Analog Input Object 11

Power Factor: Phase A

PF_A

Unitless

Analog Input Object 12

Power Factor: Phase B

PF_B

Unitless

Analog Input Object 13

Power Factor: Phase C

PF_C

Unitless

Analog Input Object 14

Voltage: Phase A-Phase B

Volts_AB

Volts

Analog Input Object 15

Voltage: Phase B-Phase C

Volts_BC

Volts

Analog Input Object 16

Voltage: Phase A-Phase C

Volts_AC

Volts

Analog Input Object 17

Voltage: Phase A-Neutral

Volts_AN

Volts

Analog Input Object 18

Voltage: Phase B-Neutral

Volts_BN

Volts

Analog Input Object 19

Voltage: Phase C-Neutral

Volts_CN

Volts

Analog Input Object 20

Current: Phase A

Current_A

Amps

Analog Input Object 21

Current: Phase B

Current_A

Amps

Analog Input Object 22

Current: Phase C

Current_A

Amps

Clear the kWh accumulator to zero by writing 0.0 to the PRESENT_VALUE property Analog Value Object 1.

Changing the Device_Instance:

• Units are shipped with a default Device Instance of 123.
• There are 2 methods of changing the Device_Instance:

1. Write the Object_Identifier directly. The Device’s Object_Identifier contains both the Object_Type (Device = 8) and the Object_Instance (0-4194302). Write
the Device’s Object_Identifier with (8,Instance) to change the Device_Instance.

2. Use Analog Value Object 2. Although a REAL (i.e. floating point) value, writing the Present_Value of AV2 is an alternative method of changing the Device_
Instance. This value may be written in the range 0-4194302. Any fractional value will be truncated (e.g. 57.234 will be written as 57).