INSTALLATIoN GUIDe
bacnet descriPtions
BACnet Object
Description
Description Field
Units
Device Object
This device
Veris H81xx Energy Meter
with H8186-CB BACnet
Communications Board
N/A
Analog Value Object 1
Accumulated Energy
kWh_Total
kWh
Analog Value Object 2
Device Instance
Device_Instance
N/A
Analog Input Object 1
Total Real Power
kW_Total
kW
Analog Input Object 2
Total Reactive Power
kVAR_Total
kW
Analog Input Object 3
Total Apparent Power
kVA_Total
kW
Analog Input Object 4
Total Power Factor
PF_Total
Unitless
Analog Input Object 5
Average Line-Line Voltage
Volts_LL_Avg
Volts
Analog Input Object 6
Average Line-Nuetral Voltage Volts_LN_Avg
Volts
Analog Input Object 7
Average Current
Current_Avg
Amps
Analog Input Object 8
Real Power: Phase A
kW_A
kW
Analog Input Object 9
Real Power: Phase B
kW_B
kW
Analog Input Object 10
Real Power: Phase C
kW_C
kW
Analog Input Object 11
Power Factor: Phase A
PF_A
Unitless
Analog Input Object 12
Power Factor: Phase B
PF_B
Unitless
Analog Input Object 13
Power Factor: Phase C
PF_C
Unitless
Analog Input Object 14
Voltage: Phase A-Phase B
Volts_AB
Volts
Analog Input Object 15
Voltage: Phase B-Phase C
Volts_BC
Volts
Analog Input Object 16
Voltage: Phase A-Phase C
Volts_AC
Volts
Analog Input Object 17
Voltage: Phase A-Neutral
Volts_AN
Volts
Analog Input Object 18
Voltage: Phase B-Neutral
Volts_BN
Volts
Analog Input Object 19
Voltage: Phase C-Neutral
Volts_CN
Volts
Analog Input Object 20
Current: Phase A
Current_A
Amps
Analog Input Object 21
Current: Phase B
Current_A
Amps
Analog Input Object 22
Current: Phase C
Current_A
Amps
Clear the kWh accumulator to zero by writing 0.0 to the PRESENT_VALUE property Analog Value Object 1.
Changing the Device_Instance:
• Units are shipped with a default Device Instance of 123.
• There are 2 methods of changing the Device_Instance:
1. Write the Object_Identifier directly. The Device’s Object_Identifier contains both the Object_Type (Device = 8) and the Object_Instance (0-4194302). Write
the Device’s Object_Identifier with (8,Instance) to change the Device_Instance.
2. Use Analog Value Object 2. Although a REAL (i.e. floating point) value, writing the Present_Value of AV2 is an alternative method of changing the Device_
Instance. This value may be written in the range 0-4194302. Any fractional value will be truncated (e.g. 57.234 will be written as 57).