User Guide: LDRA6

Chapter 2: Connections & Settings

5 970

484-6510

www.rletech.com

2-1.1 TB1 – Power

The LDRA6 connects to a 24VDC power supply using TB1, a two position connector labeled 24VDC.

2-1.2 POW1 – Power

Power can also be supplied to the unit through POW1. This is a wall adapter plug connection. This also
requires 24VDC.

2-1.3 TB2, TB3 – Zone Inputs

SeaHawk Leak Detection Cable (SC) and/or dry contact wires connect to the LDRA6 through TB2. Fifteen
foot (4.57m) leader cables (one is included in each leader cable kit, part #LC-KIT) are required for leak
detection cable connections only. Dry contact wires must be user supplied or may be supplied with your
dry contact device. Connect cables/wires as follows:

Position

Leak Detection Cable

Dry Contact Wire

TB3-1

Zone 1 White

Zone 1 Input-1

TB3-2

Zone 1 Black

Zone 1 Input-2

TB3-3

Zone 1 Green

N/A

TB3-4

Zone

1

Red

N/A

TB3-5

Zone 2 White

Zone 2 Input-1

TB3-6

Zone

2

Black

Zone

2

Input-2

TB3-7

Zone 2 Green

N/A

TB3-8

Zone

2

Red

N/A

TB3-9

Zone 3 White

Zone 3 Input-1

TB3-10

Zone

3

Black

Zone

3

Input-2

TB3-11

Zone 3 Green

N/A

TB3-12

Zone

3

Red

N/A


TB2-1

Zone 4 White

Zone 4 Input-1

TB2-2

Zone

4

Black

Zone

4

Input-2

TB2-3

Zone 4 Green

N/A

TB2-4

Zone

4

Red

N/A

TB2-5

Zone 5 White

Zone 5 Input-1

TB2-6

Zone

5

Black

Zone

5

Input-2

TB2-7

Zone 5 Green

N/A

TB2-8

Zone

5

Red

N/A

TB2-9

Zone 6 White

Zone 6 Input-1

TB2-10

Zone

6

Black

Zone

6

Input-2

TB2-11

Zone 6 Green

N/A

TB2-12

Zone

6

Red

N/A

2-1.4 TB5, TB4 – Zone Alarm Relays

These are the Zone Alarm Relay output terminal blocks (Form C). A status LED is located above each
relay, which will indicate the state of the relay (on/off). These relays can be configured as supervised or
unsupervised, latched or unlatched (unsupervised and unlatched by factory default). Connect the Zone
Alarm Relay wires to TB3 and TB4 as follows:


TB5-1 Zone 1 alarm relay normally open (NO)
TB5-2 Zone 1 alarm relay common (C)
TB5-3 Zone 1 alarm relay normally closed (NC)

TB5-4 Zone 2 alarm relay normally open (NO)
TB5-5 Zone 2 alarm relay common (C)
TB5-6 Zone 2 alarm relay normally closed (NC)