York D2EB030 User Manual
Page 13

360101-XTG-B-0508
Johnson Controls Unitary Products
13
* = KW listed is for 240 volts, use table on previous page for 208 or 230 volts.
** = KW listed is for 480 volts, use table on previous page for 460 volts.
*** = KW listed is for 600 volts, use table on previous page for 575 volts.
042
208/230-3-60
11.5
88.0
1.1
3.5
2NH04501025
1
7.5/10.0*
20.8/24.1
30.4/34.4
35/35
35/35
2NH04501525
1
11.3/15.0*
31.3/36.1
43.5/49.5
45/50
45/50
048
208/230-3-60
14.1
105.0
0.7
4.0
2NP04501025
1
7.5/10.0*
20.8/24.1
31.1/35/1
35/40
35/40
2NP04501525
1
11.3/15.0*
31.3/36.1
44.1/50.1
45/60
45/60
2NP04502025
2
15.0/20.0*
41.7/48.1
57.1/65.1
60/70
60/70
2NH04502525
2
18.8/25.0*
52.1/60.1
70.2/80.2
80/90
80/90
060
208/230-3-60
16.0
125.0
1.3
7.0
2NH04501025
1
7.5/10.0*
20.8/24.1
34.8/38.8
40/40
40/40
2NH04501525
1
11.3/15.0*
31.3/36.1
47.8/53.9
50/60
50/60
2NH04502025
2
15.0/20.0*
41.7/48.1
60.9/68.9
70/70
70/70
2NH04502525
2
18.8/25.0*
52.1/60.1
73.9/83.9
80/90
80/90
036
460-3-60
5.8
40.0
0.6
1.8
2NH04501046
1
10.0**
12
17.3
20
20
2NH04501546
1
15.0**
18
24.8
25
25
042
460-3-60
5.8
42.0
0.6
1.8
2NH04501046
1
10.0**
12
17.3
20
20
2NH04501546
1
15.0**
18
24.8
25
25
048
460-3-60
7.1
55.0
0.8
2.0
2NP04501046
1
10.0**
12
17.5
20
20
2NH04501546
1
15.0**
18
25.1
30
30
2NH04502046
2
20.0**
24.1
32.6
35
35
2NH04502546
2
25.0**
30.1
40.1
45
45
060
460-3-60
8.0
67.0
0.7
3.5
2NH04501046
1
10.0**
12
19.4
20
20
2NH04501546
1
15.0**
18
26.9
30
30
2NP04502046
2
20.0**
24.1
34.4
35
35
2NP04502546
2
25.0**
30.1
42
45
45
036
575-3-60
4.5
32.0
0.4
1.5
2NH04501058
1
10.0***
9.6
13.9
15
15
2NH04501558
1
15.0***
14.4
19.9
20
20
042
575-3-60
5.8
44.0
0.4
1.5
2NH04501058
1
10.0***
9.6
13.9
15
15
2NH04501558
1
15.0***
14.4
19.9
20
20
048
575-3-60
5.6
44.0
0.6
1.6
2NH04501058
1
10.0***
9.6
14
15
15
2NH04501558
1
15.0***
14.4
20
25
25
2NH04502058
2
20.0***
19.2
26.1
30
30
2NH04502558
2
25.0***
24.1
32.1
35
35
060
575-3-60
6.4
50.0
0.6
2.8
2NH04501058
1
10.0***
9.6
15.5
20
20
2NH04501558
1
15.0***
14.4
21.5
25
25
2NP04502058
2
20.0***
19.2
27.6
30
30
2NP04502558
2
25.0***
24.1
33.6
35
35
1. Dual element, time delay type.
2. Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.
TABLE 11: ELECTRICAL DATA (COOLING / ELECTRIC HEAT) (CONTINUED)
MODEL
DEB
POWER
SUPPLY
COMPRESSOR
COND. FAN
MOTORS
SUPPLY
AIR
BLOWER
MOTOR
ELECTRIC HEAT ACCESSORY
MCA
(AMPS)
MAX FUSE/
SIZE
1
(AMPS)
MAX HACR
2
BREAKER SIZE
RLA
LRA
FLA
FLA
MODEL NO.
STAGE
KW
TOTAL AMPS