York H*RD018 THRU 060 User Manual
Page 23
254892-YTG-C-0606
Unitary Products Group
23
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
*
= Single-phase outdoor units only.
*
= Single-phase outdoor units only.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
H2RD060S06, H1RD060S(25,46)**
INDOOR COIL MODEL NO.
FC/MC/PC/UC60
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
1650
1900
2150
ID
DB
(°F)
80 80
75
80
80
80 80 75
80
80 80 80
75 80 80
ID
WB
(°F)
57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C.
57.2 57.4 54.0 59.6 59.1 58.9 59.1 55.2 60.4 61.1 60.6 60.8 56.3 61.2 63.1
S.C.
52.1 48.7 39.6 38.8 28.1 54.1 51.9 42.7 42.0 31.1 56.1 55.2 45.7 45.3 34.1
KW
3.0 3.1 3.1 3.1 3.1 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
75
T.C.
54.9 55.1 51.6 57.2 57.0 56.9 56.8 52.7 58.1 58.2 59.0 58.5 53.8 59.0 59.5
S.C.
50.0 47.4 38.6 38.0 27.7 52.1 50.5 41.6 41.1 30.0 54.2 53.6 44.7 44.2 32.3
KW
3.5 3.5 3.5 3.6 3.6 3.5 3.5 3.5 3.6 3.6 3.5 3.5 3.5 3.6 3.6
85
T.C.
52.6 52.9 49.3 54.8 54.8 54.9 54.5 50.3 55.8 55.4 57.3 56.1 51.2 56.9 55.9
S.C.
48.0 46.1 37.6 37.3 27.3 50.1 49.0 40.6 40.2 28.8 52.3 52.0 43.6 43.2 30.4
KW
4.0 4.0 4.0 4.0 4.1 4.0 4.0 4.0 4.0 4.1 4.0 4.0 4.0 4.0 4.1
95
T.C.
50.2 50.7 46.9 52.4 52.7 52.9 52.2 47.8 55.0 52.5 55.6 53.7 48.7 54.7 52.3
S.C.
45.9 44.8 36.5 36.5 26.9 48.1 47.6 39.5 39.6 27.7 50.4 50.4 42.5 42.1 28.5
KW
4.4 4.4 4.4 4.4 4.6 4.5 4.4 4.4 4.5 4.6 4.5 4.4 4.4 4.5 4.6
105
T.C.
48.3 48.2 44.9 49.9 49.4 50.5 49.9 45.3 50.8 49.2 52.8 51.6 45.6 51.6 49.0
S.C.
43.9 43.2 35.6 35.4 25.7 46.0 45.6 38.4 38.1 26.8 48.0 47.9 41.1 40.8 28.0
KW
5.1 5.0 5.1 5.1 5.2 5.1 5.1 5.1 5.1 5.2 5.1 5.1 5.1 5.1 5.2
115
T.C.
46.4 45.9 43.0 47.5 46.1 48.2 47.7 42.8 48.1 46.0 50.0 49.6 42.5 48.6 45.9
S.C.
42.0 41.7 34.7 34.4 24.6 43.9 43.6 37.2 37.0 26.0 45.7 45.5 39.8 39.5 27.5
KW
5.7 5.7 5.7 5.7 5.8 5.7 5.7 5.7 5.7 5.8 5.7 5.7 5.7 5.7 5.8
125
T.C.
44.5 43.5 41.1 45.1 42.9 45.8 45.5 40.3 45.3 42.8 47.2 47.6 39.5 45.6 42.7
S.C.
40.1 40.2 33.7 33.4 23.5 41.8 41.6 36.1 35.8 25.2 43.4 43.1 38.4 38.3 26.9
KW
6.3 6.3 6.3 6.3 6.4 6.3 6.3 6.3 6.3 6.5 6.3 6.4 6.3 6.3 6.5
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
**
For three-phase, decrease T.C. by 0.5 and S.C. by 0.3.
Air Handler
Coil
T.C.
S.C.
KW
MA20D
MC60D
1.00 1.00 1.00
MA20D
MC61D
1.01 1.01 1.01
MA20D
G*FD060H24
1.00 1.00 1.00
MA20D
G*FD061H24
1.01 1.01 1.01
AHP/SHP60
–
1.00 1.02 1.00
F*FV060*
–
1.00 1.02 1.00
MV20D*
FC/MC60D
0.98 0.97 0.98
MV20D*
MC61D
1.01 0.99 1.01
AV/SV60*
–
1.00 1.02 1.00
–
MC61
1.01 1.01 1.01
–
HC60
1.00 1.00 1.00
–
HD60
1.00 1.01 1.00
–
G*FA060S21,24
1.00 1.00 1.00
–
G*FD060H24
1.00 1.00 1.00
–
G*FD061H24
1.01 1.01 1.01
MA20D
MC60D
1.00 1.00 1.00
Variable Speed
Furnace*
Coil
T.C.
S.C.
KW
P(C,V)9*D20
FC/MC/PC60D 0.99
0.96
0.99
PV8*C20
FC/PC60C 0.98
0.98
0.98
P(C,V)9*C20
FC/PC60C 0.99
0.96
0.99
PV8*C20
HC60 0.98
0.98
0.98
P(C,V)9*D20
HC60 0.99
0.96
0.99
PV8*C20
HD60 1.00
0.99
1.00
P(C,V)9*C20
HD60 0.99
0.96
0.99
P(C,V)9*D20
HD60 0.98
0.96
0.98
PV8*C20
MC61D 1.00
0.99
1.00
P(C,V)9*C20
MC61D 0.98
0.96
0.98
P(C,V)9*D20
MC61D 1.00
0.96
1.00