beautypg.com

York H*RD018 THRU 060 User Manual

Page 19

background image

254892-YTG-C-0606

Unitary Products Group

19

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

*

= Single-phase outdoor units only.

*

= Single-phase outdoor units only.

COOLING PERFORMANCE DATA

AIR CONDITIONER MODEL NO.

H2RD030S06 , H1RD030S(25,46) **

INDOOR COIL MODEL NO.

FC/MC/PC/UC30

CONDENSING

ENTERING AIR

TEMPERATURE

IDCFM

800

1000

1200

ID

DB

(°F)

80 80

75

80

80

80 80 75

80

80 80 80

75 80 80

ID

WB

(°F)

57 62 62 67 72 57 62 62 67 72 57 62 62 67 72

65

T.C.

27.0 31.8 30.1 33.7 35.6 29.0 33.4 31.3 35.1 36.7 31.1 35.0 32.6 36.5 37.7

S.C.

26.9 24.7 20.6 21.2 16.0 29.0 27.7 22.9 23.4 17.7 31.1 30.7 25.2 25.6 19.5

KW

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

75

T.C.

25.9 30.3 28.7 32.1 33.6 27.9 31.9 29.9 33.4 34.5 29.8 33.5 31.1 34.7 35.4

S.C.

25.9 24.2 20.0 20.5 15.6 27.8 27.0 22.3 22.7 17.2 29.8 29.8 24.5 24.9 18.8

KW

1.9 1.9 1.9 2.0 2.0 1.9 1.9 1.9 2.0 2.0 2.0 1.9 2.0 2.0 2.0

85

T.C.

24.9 28.8 27.2 30.4 31.7 26.7 30.4 28.4 31.7 32.4 28.6 32.0 29.6 32.9 33.1

S.C.

24.9 23.7 19.5 19.7 15.2 26.7 26.3 21.7 21.9 16.7 28.5 28.9 23.9 24.1 18.1

KW

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.2 2.1 2.1 2.1 2.1 2.2

95

T.C.

23.8 27.4 25.8 28.7 29.7 25.6 28.9 26.9 30.0 30.2 27.3 30.5 28.1 31.2 30.7

S.C.

23.8 23.2 18.9 18.9 14.8 25.5 25.6 21.1 21.2 16.2 27.3 28.1 23.3 23.4 17.5

KW

2.2 2.2 2.2 2.3 2.3 2.2 2.2 2.2 2.3 2.3 2.3 2.3 2.2 2.3 2.3

105

T.C.

22.8 25.9 24.3 27.1 27.8 24.4 27.5 25.3 28.2 28.2 26.0 29.1 26.4 29.3 28.5

S.C.

22.7 22.4 18.3 18.3 14.1 24.3 24.5 20.4 20.5 15.4 25.9 26.5 22.6 22.6 16.6

KW

2.4 2.4 2.4 2.4 2.5 2.4 2.4 2.4 2.4 2.5 2.4 2.4 2.4 2.5 2.5

115

T.C.

21.8 24.5 22.8 25.5 25.9 23.2 26.1 23.7 26.5 26.1 24.7 27.8 24.7 27.4 26.4

S.C.

21.7 21.6 17.6 17.7 13.5 23.2 23.3 19.7 19.8 14.6 24.7 25.0 21.8 21.9 15.8

KW

2.5 2.5 2.5 2.6 2.6 2.6 2.5 2.5 2.6 2.7 2.6 2.6 2.5 2.6 2.7

125

T.C.

20.8 23.0 21.3 23.9 24.0 22.1 24.8 22.2 24.7 24.1 23.4 26.5 23.0 25.6 24.3

S.C.

20.6 20.9 17.0 17.1 12.8 22.0 22.2 19.0 19.1 13.9 23.4 23.5 21.1 21.1 15.1

KW

2.7 2.7 2.6 2.7 2.8 2.7 2.7 2.7 2.7 2.8 2.8 2.7 2.7 2.8 2.8

NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
**

For three-phase, decrease T.C. by 0.6 and S.C. by 0.3.

Air Handler

Coil

T.C.

S.C.

KW

MA12B

MC30B

1.00 1.00 1.00

MA12B

MC36B

1.00 1.01 1.00

MA12B

G*FD036H17

1.00 1.01 1.00

AHP30

1.01 1.04 1.01

AHP36

1.01 1.08 1.01

F*FP036

1.00 1.01 1.00

MV12B*

FC/MC30B

1.01 1.00 0.97

MV12B*

FC/MC36B

1.01 1.01 0.97

MV16C*

FC/MC36C

1.01 1.01 0.97

AV36*

1.01 1.01 0.97

FC/MC/PC/UC36

1.00 1.01 1.00

HC30

1.00 1.03 1.00

HC36

1.01 1.04 1.01

HD36

1.01 1.05 1.01

G*FA036S14

1.00 1.00 1.00

G*FD036H17

1.00 1.00 1.00

G*FD036H21

1.00 1.00 1.00

Variable Speed
Furnace

Coil

T.C.

S.C.

KW

PV8*A12

FC/MC/PC30A 1.01

1.00

1.01

PV9*A12

FC/MC/PC30A 1.01

1.02

0.97

PV8*B16

FC/MC/PC30B 1.01

1.00

1.01

P(C,V)9*B12

FC/MC/PC30B 1.01

1.00

1.01

PV8*A12

FC/MC/PC36A 1.01

1.02

1.01

PV9*A12

FC/MC/PC36A 1.01

1.03

0.97

PV8*B16

FC/MC/PC36B 1.01

1.03

0.97

P(C,V)9*B12

FC/MC/PC36B 1.01

1.03

0.97

PV8*C16

FC/MC/PC36C 1.01

1.02

1.01

PV8*C20

FC/MC/PC36C 1.01

1.02

1.01

P(C,V)9*C16

FC/MC/PC36C 1.01

1.02

0.97

P(C,V)9*C20

FC/MC/PC36C 1.01

1.02

0.97

PV8*A12

HC30 1.01

1.03

0.97

PV9*A12

HC30 1.01

1.03

0.97

PV8*B16

HC36 1.01

1.05

0.97

P(C,V)9*B12

HC36 1.01

1.05

0.97

PV8*A12

HD36 1.01

1.05

0.97

PV8*B16

HD36 1.01

1.06

0.97

PV8*C16

HD36 1.01

1.06

0.97

PV8*C20

HD36 1.01

1.06

0.97

PV9*A12

HD36 1.01

1.05

0.97

P(C,V)9*B12

HD36 1.01

1.06

0.97

P(C,V)9*C16

HD36 1.01

1.06

0.97

P(C,V)9*C20

HD36 1.01

1.06

0.97

This manual is related to the following products: