beautypg.com

York H*RD018 THRU 060 User Manual

Page 21

background image

254892-YTG-C-0606

Unitary Products Group

21

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

*

= Single-phase outdoor units only.

*

= Single-phase outdoor units only.

COOLING PERFORMANCE DATA

AIR CONDITIONER MODEL NO.

H2RD042S06 , H1RD042S(25,46) **

INDOOR COIL MODEL NO.

FC/MC/PC/UC42

CONDENSING

ENTERING AIR

TEMPERATURE

IDCFM

1200

1400

1600

ID

DB

(°F)

80 80

75

80

80

80 80 75

80

80 80 80

75 80 80

ID

WB

(°F)

57 62 62 67 72 57 62 62 67 72 57 62 62 67 72

65

T.C.

39.6 44.0 42.6 46.7 50.0 41.5 45.0 43.4 47.6 50.4 43.4 46.0 44.3 48.5 50.8

S.C.

39.3 37.3 30.7 31.1 23.6 41.0 39.7 33.1 33.3 24.7 42.7 42.2 35.5 35.5 25.7

KW

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

75

T.C.

38.0 41.8 40.3 44.4 47.2 40.0 42.9 41.1 45.2 47.7 41.9 43.9 41.9 46.0 48.1

S.C.

37.6 36.1 29.8 30.0 22.7 39.3 38.5 32.0 32.2 23.8 40.9 40.8 34.2 34.4 24.8

KW

2.5 2.5 2.5 2.5 2.6 2.5 2.5 2.5 2.5 2.6 2.5 2.5 2.5 2.5 2.6

85

T.C.

36.4 39.6 38.0 42.1 44.4 38.4 40.7 38.7 42.8 44.9 40.4 41.9 39.4 43.4 45.4

S.C.

36.0 34.9 28.8 28.9 21.8 37.6 37.2 30.9 31.1 22.9 39.2 39.5 33.0 33.4 24.0

KW

2.7 2.7 2.7 2.7 2.8 2.7 2.7 2.7 2.7 2.8 2.7 2.7 2.7 2.8 2.8

95

T.C.

34.7 37.4 35.7 39.8 41.6 36.9 38.6 36.3 40.5 42.2 39.0 39.8 36.9 40.9 42.8

S.C.

34.3 33.8 27.8 27.8 20.8 35.9 36.0 29.8 29.6 22.0 37.4 38.2 31.7 32.3 23.1

KW

2.9 2.9 2.9 3.0 3.1 2.9 2.9 2.9 3.0 3.1 2.9 2.9 2.9 3.0 3.1

105

T.C.

33.3 35.6 33.5 37.4 39.0 35.2 36.7 34.1 37.9 39.4 37.2 37.7 34.7 38.4 39.8

S.C.

32.1 32.6 26.9 26.9 19.8 33.8 34.5 28.8 29.0 21.0 35.6 36.3 30.8 31.2 22.2

KW

3.1 3.1 3.1 3.2 3.3 3.1 3.1 3.1 3.2 3.3 3.2 3.2 3.1 3.2 3.3

115

T.C.

31.9 33.8 31.4 35.1 36.4 33.6 34.7 31.9 35.6 36.6 35.4 35.7 32.5 36.0 36.8

S.C.

31.4 31.5 26.0 26.0 18.9 32.6 33.0 27.9 28.0 20.1 33.8 34.5 29.8 30.1 21.3

KW

3.3 3.3 3.3 3.4 3.5 3.4 3.4 3.3 3.4 3.5 3.4 3.4 3.4 3.4 3.6

125

T.C.

30.5 32.0 29.2 32.8 33.9 32.1 32.8 29.8 33.2 33.9 33.6 33.7 30.3 33.6 33.9

S.C.

30.0 30.4 25.2 25.1 17.9 31.0 31.5 27.0 27.0 19.1 32.1 32.6 28.8 28.9 20.4

KW

3.5 3.5 3.5 3.6 3.8 3.6 3.6 3.5 3.6 3.8 3.6 3.6 3.6 3.7 3.8

NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
**

For three-phase, decrease T.C. by 1.0 and S.C. by 0.7.

Air Handler

Coil

T.C.

S.C.

KW

MA12C

MC42C

1.00 1.00 1.00

MA14D

MC42D

1.00 1.00 1.00

MA12C

MC48C

1.01 1.02 1.01

MA14D

MC48D

1.01 1.02 1.01

MA12C

G*FD042H21

1.00 1.00 1.00

MA12C

G*FD048H21

1.01 1.02 1.01

AHP42

1.01 1.05 1.01

AHP/SHP48

1.04 1.04 1.04

AHP/SHP60

1.00 1.12 0.96

F*FP048

1.01 1.05 1.01

MV16C*

FC/MC42C

1.00 0.98 1.00

MV16C*

FC/MC48C

1.02 1.00 0.98

MV20D*

FC/MC48D

1.02 1.01 0.98

AV/SV48*

1.00 0.98 1.00

FC/MC/PC/UC48

1.01 1.02 1.01

HC48

1.01 1.01 1.01

HD48

1.02 1.00 1.02

G*FA048S17

1.00 1.00 1.00

G*FA048S21

1.01 1.02 1.01

G*FD042H21

1.00 1.00 1.00

G*FD046H17

1.00 1.00 1.00

G*FD048H21,24

1.01 1.02 1.01

Variable Speed
Furnace

Coil

T.C.

S.C.

KW

PV8*B16

FC/MC/PC42B 1.00

1.00

1.00

PV8*C16

FC/MC/PC42C 1.00

1.00

1.00

PV8*C20

FC/MC/PC42C 1.00

1.00

1.00

PV8*C16

FC/MC/PC48C 1.02

1.02

1.02

PV8*C20

FC/MC/PC48C 1.02

1.02

0.98

P(C,V)9*C16

FC/MC/PC48C 1.02

1.02

1.02

P(C,V)9*C20

FC/MC/PC48C 1.02

1.02

1.02

P(C,V)9*D20

FC/MC/PC48D 1.02

1.02

1.02

PV8*C16

HC48 1.01

1.01

1.01

PV8*C20

HC48 1.02

1.02

1.02

P(C,V)9*C16

HC48 1.01

1.01

1.01

P(C,V)9*C20

HC48 1.01

1.02

1.01

PV8*C16

HD48 1.04

1.03

0.99

PV8*C20

HD48 1.04

1.03

0.99

P(C,V)9*C16

HD48 1.04

1.03

1.04

P(C,V)9*C20

HD48 1.04

1.03

0.99

P(C,V)9*D20

HD48 1.04

1.03

0.99

This manual is related to the following products: