beautypg.com

Wiring, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 56

background image

Part number 550-142-054/0411

GV90+

gas

-

fired

water

boiler

— Boiler Manual

56

Wiring

For your safety, turn off electrical power supply at service

entrance panel before making any electrical connections

to avoid possible electric shock hazard. Failure to do so

can cause severe personal injury or death.

Installation must comply with:

National Electrical Code and any other national, state, provincial or

local codes or regulations. In Canada, CSA C22.1 Canadian Electrical

Code Part 1, and any local codes. Boiler must be electrically grounded as

required by National Electrical Code ANSI/NFPA 70-latest edition.

Wiring must be N.E.C. Class 1. Boiler must be electrically

grounded as required by National Electrical Code ANSI/

NFPA 70-latest edition.

To replace wiring, order complete harness assemblies

from Weil-McLain. If any original wiring as supplied with

boiler must be replaced, and a harness is not immediately

available, use only type 105°C wire or equivalent. Use this

wiring only as a temporary repair. Obtain a complete

harness from Weil-McLain.

Wiring connections

Power wiring

Connect 120 VAC power wiring as shown in Figure 66. The junction
box is located on the inside left jacket panel.

Watch the polarity of the circuit when connecting the

120 VAC power wiring. If the polarity is switched, the

integrated boiler control will lockout. The IBC will

flash the POWER light to indicate this problem. See the

troubleshooting information beginning on page 75.

Additional limit controls

Wire additional limit controls (if used) as shown in Figure 67.

Thermostat(s)

Install thermostats on inside walls, away from influences of drafts,

hot or cold water pipes, lighting fixtures, television, sun rays, or fire-

places.

Follow instructions with thermostat. If it has a heat anticipator, set heat

anticipator in thermostat to match power requirements of equipment

connected to it (ignition control and gas valve, zone valve contacts,

etc.). Wiring diagram on boiler gives setting for standard equipment

(ignition control and gas valve).

Thermostat wires are labeled “T-T” on boiler. Remove label before

connecting as shown in Figure 66. Route this wiring through the hole

in the upper left side jacket.

For zoned systems, substitute the zone valve end switches or circulator

relay contacts for the thermostat contact shown in Figure 66.

Figure 66

Field wiring connections — service switch

and thermostat (or end switch) provided

by installer

When using three-wire zone valves, take care

to avoid mis-wiring. This can impose an ad-

ditional 24 volts across the boiler control circuitry. The IBC

will sense this problem and lockout. It will flash the POW-

ER and TSTAT CIRC lights to indicate the problem. See

label on IBC for explanation of lockout conditions. To

verify before connecting to boiler, disconnect field thermo-

stat wires at boiler. Place a voltmeter across the leads. Then

watch the voltmeter as each zone is activated (by activating

zone thermostat). There should never be a voltage reading

across the two leads coming to the boiler. If you see a volt-

age reading, one or more zone valves is mis-wired.

Carbon monoxide detector

For

Direct Exhaust

units, a carbon monoxide

detector is required in the boiler room. The

carbon monoxide detector must be wired on

the same electrical circuit as the boiler. For

Direct Vent

units, a carbon monoxide detector

that is wired on the same electrical circuit as

the boiler is strongly recommended.

Figure 67

Wiring location for additional limit controls