Gas piping, Gv90, Boiler manual – Weil-McLain GV90+ User Manual
Page 55: Natural gas, Propane gas

Part number 550-142-054/0411
55
GV90+
gas
-
fired
water
boiler
— Boiler Manual
Figure 65
Pipe capacity for 0.60 specific gravity natural gas
Gas pipe
length
(feet)
Capacity in cubic feet of gas per hour
Natural gas only, with specific gravity of 0.60
Based on pressure drop of 0.3” w.c.
Gas pipe diameter —
½”
¾”
1”
1¼”
1½”
10
132
278
520
1050
1600
20
92
190
350
730
1100
30
73
152
285
590
860
40
63
130
245
500
760
50
56
115
215
440
670
75
45
93
175
360
545
100
38
79
150
305
460
150
31
64
120
250
380
For additional gas pipe sizing information, refer to ANSI Z223.1 (or
B149.1 orB149.2 for Canadian installations).
Gas piping
(continued)
Natural Gas
1. Refer to Figure 65 for pipe length and diameter.
Size gas supply piping for total flow to all connected
appliances. For each GV90+ boiler, provide for the
following gas flow (cfh = cubic feet per hour):
Boiler model
CFH natural gas
GV90+3
70
GV90+4
140
GV90+5
105
GV90+6
175
2. Inlet pressure required at gas valve inlet:
• maximum 13” w.c.
• minimum 4” w.c.
Install 100% lockup gas pressure regula-
tor in supply line if inlet pressure exceeds
13” water column. Adjust for 13” w.c.
maximum.
Propane Gas
1. Contact gas supplier to size pipes, tanks and 100%
lockup gas pressure regulator.
2. Adjust propane supply regulator provided by gas
supplier for 13” w.c. maximum pressure.
3. Inlet pressure required at gas valve inlet:
• maximum 13” w.c.
• minimum 4” w.c.