beautypg.com

Direct exhaust — sidewall, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 51

background image

Part number 550-142-054/0411

51

GV90+

gas

-

fired

water

boiler

— Boiler Manual

DIRECT EXHAUST — Sidewall

DO NOT sidewall vent DIRECT EX-

HAUST APPLICATIONS

at altitudes

above 5,500 feet. Sidewall venting is
only allowed for

DIRECT VENT

ap-

plications (ducted combustion air)
at altitudes above 5,500 feet.

Allowable vent/air pipe materials &

lengths

Use only the vent materials and kits

listed in Figure 40, page 33. Provide
pipe adapters if specified.

1. Locate the termination such that the total air

piping and vent piping from the boiler to the
termination will not exceed the maximum
length given in Figure 39, page 32.

Determine termination location

1. The air and vent terminations must be

installed as shown in Figure 61 and in Fig-
ure 62, page 52.

2. The terminations must comply with clearances

and limitations shown in Figure 41, page 35.

3. Locate the termination so it is not likely to be

damaged by foreign objects, such as stones
or balls, or subject to buildup of leaves or
sediment.

Multiple vent/air terminations

1. Terminate each vent of multiple direct exhaust

GV90+ boilers as described in this manual for
individual vents.

2. Space terminations as required for best instal-

lation practices and required maintenance.

a. External venting greater than 4 feet

requires an enclosure around the vent
pipe. The vent termination must exit
through the enclosure as shown in Fig-
ure 61, page 51, maintaining all required
clearances.

Prepare wall penetration

Where the vent penetrates an outside

wall, the annular space around the
penetration must be permanently
sealed using approved materials to
prevent entry of combustion prod-
ucts into the building.

1. Wall penetration:

a. Cut a rough opening large enough to clear

the diameter of the metal thimble used.

Figure 61

INSTALLATION SEQUENCE — Direct exhaust sidewall

Step 1 Read and follow all instructions in this manual. DO NOT proceed with

vent installation until you have read page 29 through page 35,

page 49 and page 50.

Step 2 Install the boiler in a location that allows proper routing of vent piping to

the selected sidewall location.

Step 3 Make sure the selected sidewall termination location complies with Fig-

ure 41, page 35.

Step 4 Use only the vent materials listed in Figure 40, page 33. Provide pipe adapt-

ers where required. Vent piping length must not exceed the value shown in
Figure 39, page 32.

Step 5 Prepare the sidewall penetration and secure the sidewall plate as instructed

in this section. See “Prepare wall penetration” on page 51 and “Termination
and fittings” on page 52.

Step 6 The vent piping can terminate using the Weil-McLain vent/air plate (without

air piping connected). It can also terminate using a coupling or down-turned
elbow, or snorkeled and terminated with an elbow. See illustration above.
The coupling or elbow must butt against the outside plate.

Step 7 Install vent piping between the boiler and the sidewall opening. Slope

horizontal piping downward toward the boiler at least 1/4 inch per foot.
See page 48 for general guidelines.

Step 8 Install pipe supports every 5 feet on both the horizontal and vertical runs.

Install a hanger support within 6 inches of any upturn in the piping.

Step 9 Attach the vent termination exterior piping, if used: Use any of the con-

figurations shown above, as needed to ensure clearance above grade or
snow line.

Step 10 The vent pipe may run up as high as 4 feet with no enclosure. The vent

pipe must be secured with braces, and all clearances and lengths must be
maintained. Space braces no further than 24 inches apart.

Step 11 External venting greater than 4 feet requires an insulated enclosure around

the vent and air pipes. The vent and air terminations must exit through

the enclosure as shown in the illustration above, maintaining all required
clearances.