beautypg.com

Venting & air — general, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 33

background image

Part number 550-142-054/0411

33

GV90+

gas

-

fired

water

boiler

— Boiler Manual

Venting & air — general

(cont.)

Figure 40

Vent and air piping materials — Use only the materials listed below, ensuring that all materials meet

local codes

Item

Material

Standards for installations in:

United States

Canada

Plastic piping materials

Vent or air pipe

&

fittings

PVC schedule 40

ANSI/ASTM D1785

Plastic vent pipe must be certified to

ULC S636 when required. (Note 2)

Air pipe can be any of those listed at

left if acceptable for local codes.

PVC-DWV (Note 1)

ANSI/ASTM D2665

CPVC schedule 40 (Note 1)

ANSI/ASTM F441

ABS-DWV schedule 40 (Note 1)

ANSI/ASTM D2661

PVC & ABS pipe

cement & primer

PVC

ANSI/ASTM D2564

CPVC (Note 1)

ANSI/ASTM F493

ABS (Note 1)

ANSI/ASTM D2235

AL29-4C piping materials

Vent pipe

AL29-4C

stainless

steel

Heat Fab, Inc. — Saf-T-Vent

®

Z-Flex, Inc. — Z-Vent II

Dura-Vent — FasNSeal™

Metal-Fab, Inc. — CORR/GUARD

Certified for Category IV and direct vent

appliance venting

Weil-McLain bird screens (purchase separately)

Weil-McLain

bird screens

3” vent screen:

W-M part number 383-500-105

Note 1:

DO NOT use DWV, CPVC or ABS when using concentric vent termination. Use ONLY PVC schedule 40.

Note 2:

IPEX PVC concentric terminations utilize PVC pipe/fittings certified to ULC S636. Where ULC S636 compliance is required, use

only IPEX System 636 pipe, fittings and cement.

AL29-4C vent piping — Install a PVC-to-stainless adapter supplied by the vent pipe manufacturer at the boiler vent connection

and at the termination (when using Weil-McLain plate or concentric PVC termination). DO NOT mix piping from different vent

pipe manufacturers unless using adapters specifically designed for the purpose by the manufacturer.

Plastic piping — Do not attempt to connect different types of plastic piping together.

DO NOT use cellular core pipe.

ALL vent and air pipes require a

BIRD SCREEN at each termination

. Most kits do not

include the bird screens. Purchase bird screens separately from Weil-McLain or vent kit

supplier if not included. [Note — bird screening is integral to the Weil-McLain sidewall vent

cap, supplied standard with all GV90+ boilers. No additional screening is required.]