Gas piping, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 54

background image

Part number 550-142-054/0411

GV90+

gas

-

fired

water

boiler

— Boiler Manual

54

Gas piping

Connecting gas supply piping

Do not connect gas supply to boiler or at-

tempt to operate boiler unless the correct

orifice plate has been verified or installed

in accordance with page 8.

Except where otherwise instructed in

this manual, do not attempt to measure

or adjust the outlet pressure setting of

the gas valve.

The gas valve is factory

set to a slight negative pressure, and is

operated as a negative-pressure regulated

valve.

Failure to comply will result in malfunc-

tion of the boiler, causing severe personal

injury, death or substantial property

damage.

1. Refer to Figure 64 to connect gas supply to ½” NPT

boiler gas connection. Use wrench to hold factory-

installed gas cock.

2.

Support piping with hangers

, not by boiler or its

accessories.

3. Purge all air from gas supply piping.

4. Before placing boiler in operation, check boiler and

test all gas connections for leaks.

Do not check for gas leaks with an

open flame

use bubble test

. Failure

to use bubble test or check for gas leaks

can cause severe personal injury, death or

substantial property damage.

Close manual main shutoff valve dur-

ing any pressure testing at less than

13” w.c.

Disconnect boiler and gas valve from

gas supply piping during any pressure

testing greater than 13” w.c.

5.

Use pipe dope compatible with propane gases

.

Apply sparingly only to male threads of pipe joints

so that pipe dope does not block gas flow.

Failure to apply pipe dope as detailed

above can result in severe personal injury,
death or substantial property damage.

Figure 64

Gas supply connection to GV90+ boiler gas manifold

Honeywell VK8115V-1176 gas valve

• The Honeywell VK8115V-1176 gas valve operates with DC

voltage.

• The black power plug that connects to the gas valve contains

a DC rectifier.

• When the gas valve is energized, approximately 19 to 21 volts

DC voltage should be measured across the two outer pins of the

gas valve connector plug.

• There are 4 pins on the gas valve and 3 pin receptacles in the plug.

Only the two outer pins are used for powering the valve.

• To measure voltage, remove the screw and slightly lift the plug

until meter leads can touch end pins.

• Run boiler and test for proper voltage.
• Remember to re-install plug and tighten screw after testing.

Continuity cannot be checked in the gas valve con-

nector plug wiring due to the rectifier.